60
K100000000S9 036103 130121
OK
13.1.1
Menu→Diagnostic→Sensors
Example:
15/06/18 10:00
SENSORS
►S1: O2 OK
S2: CO OK
S3: NO OK
15/06/18 10:00
SENSORS
►S1: O2 OK
S2: CO OK
S3: NO OK
15/06/18 10:00
SENSOR S1
S.N. 00000000
Code
AACSE15
Gas O2
Range 0-25 %
Is 101.000 uA
Measured Gas
Sensor measurement range
Sensor serial number
Is sensor current
Sensor code
KEY
DESCRIPTION
Returns to the previous screen.
Selects the available parameters.
Shows the details about the selected sensor.
ESC
>
>
Messages on the state and calibration of the electrochemical sensors:
Ok
No problem detected
absent
The sensor was not detected
err data
Memory data error of the sensor
unknown
It is necessary to update the FW of the device
err pos
The sensor has been installed in the wrong position
err cal
Calibration error (sensor not calibrated)
err curr
Currents outside the range
err cfg
Do not use this sensor as it has not been accepted on
the screen "types of sensors".