Mounting:

The power supply rating on unit rating plate must comply with mains rating.

 

 

Always disconnect the power supply before opening the unit.

The heat load to be dissipated from enclosure should not exceed specific cooling output of the unit at any
condition. At cooling unit selection always cater for a safety margin of at least 15% extra cooling output in the
worst conditions. Air inlets and outlets must be completely free from obstruction.
Ensure that flows of air leaving and entering the cooling unit, internal and external, are not obstructed. Cooling
unit enclosure air suction hole must be installed in the highest possible point. When installing the unit on a door
ensure it can take the weight.
Before drilling the enclosure ensure the fixing elements and couplings will not interfere with the equipment
inside the enclosure itself. Disconnect power before starting any work inside the enclosure. Following this 1:1
Scale Drilling Template drill the holes and make the required cuts on the enclosure. This template may have
been affected by storage conditions, please check this template by verifying values of the largest dimensions
before drilling. Fit the sealing strip on the cooling unit on the side connected to the enclosure and follow the
installation diagram.

This AC unit can only be mounted to a suitably Type rated enclosure to maintain it's Type rating. The Type and
IP rating of the enclosure should be the same or higher than that of the unit.

8. Condensate management

High humidity and low temperatures inside the enclosure can lead to condensation on the evaporator.
Condensate that flows back into the enclosure can damage sensitive control electronics. The integrated
condensate evaporation of the cooling unit releases the condensate to the environment. If condensate
formation is too great, additional condensate can drip into an overflow trough, which then drains off on the
ambientt side.In order to prevent the formation of excessive condensate, you should nevertheless:

- check the seals at regular intervals
- consider installing a door contact switch (order no. 3100001). This can prevent condensation forming
when enclosure door is left open.

Condensation drain pipe connection:

The condensation drain is in the base of the unit. The condensation drain pipe should be attached as required
e.g. in conditions of high humidity. 

Содержание 87251082USL

Страница 1: ...ons 3 4 Settings 4 5 Functional principle 5 6 Technical data 6 7 Mounting 7 8 Condensate management 8 9 Mounting Principle 9 10 Electrical connection 10 11 Controller 12 12 Wiring diagram 16 13 Taking...

Страница 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage Indicates...

Страница 3: ...ad with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid sa...

Страница 4: ...t air does not come into contact with the ambient air which may well be dirty or polluted Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclo...

Страница 5: ...erant thus taking it to high pressure and high temperature and pushes it through the condenser where it is cooled by ambient air thus passing from the gas to the liquid state At the liquid state it th...

Страница 6: ...osure 360 520 cfm Mounting Wall mounted Housing Material Stainless steel AISI 304 V2A Dimension H x W x D 35 x 15 6 x 12 inch Weight 104 lbs Voltage Frequency 120 V 50 60 Hz UL Voltage Frequency 120 V...

Страница 7: ...e cut packaging opening facing up STEP 2 Pull o the packaging opening STEP 3 Hang the transport loop of the unit in the transport hook and lift it slightly STEP 4 Pull o the packaging and slide out th...

Страница 8: ...by storage conditions please check this template by verifying values of the largest dimensions before drilling Fit the sealing strip on the cooling unit on the side connected to the enclosure and fol...

Страница 9: ...ithin the rst 15 minutes after installation Use only the supplied mounting hardware Tighten Screws to 4 5 Nm Ensure the mounting surface does not warp after assembly and reinforce it if necessary 1 M6...

Страница 10: ...if closed Door contact terminals bridged or NC door switch connected contact must be closed when cabinet door is closed c68 1 ON if open Remove bridge or NO door switch connected contact must be open...

Страница 11: ...2022 Doc No 9987251082USL 11 20 SCCR Refer to UL508A Supplement SB and Seifert Systems document Short Circuit Current Rating SCCR on methods how to modify the available short circuit current within a...

Страница 12: ...ress 2 Alarm relay active 3 Heater relay active 4 Ambient blower relay active Alarm Flashes when alarms are active Heating mode Signals operation of unit in heating mode Cooling mode Signals operation...

Страница 13: ...e C 0 F 1 P25 for low temperature alarm threshold default 10 C 14 F P26 for high temperature alarm threshold default 55 C 131 F c68 for door contact NO NC logic change 0 ON if closed 1 ON if open Cont...

Страница 14: ...with an icon ashing triangle alternating with the standard display If more than one error occurs these are shown in sequence on the display Failure Code Description Solution OFF Door open Close the en...

Страница 15: ...button for at least 5 seconds When pressing PRG for 3 seconds the rmware revision code is displayed for 2 seconds When cleaning the controller panel do not use ethanol hydrocarbons ammonia or their by...

Страница 16: ...Version Nr 1 9 14 03 2022 Doc No 9987251082USL 16 20 12 Wiring diagram Power connector 1 L1 2 3 N 4 PE Signal connector 1 Alarm NC 2 Alarm COM 3 Alarm NO 4 Door contact 5 Door contact...

Страница 17: ...sor don t work Enclosure temperature is below setting temperature St Verify values of parameter St Door switch contact is open Verify door switch Controller doesn t work Replace controller Internal fa...

Страница 18: ...d be replaced immediately Do not use a steam jet or high pressure to clean the lter mats Do not wring out the lter mats If the ambient air is extremely oily we recommend the use of metal lters see acc...

Страница 19: ...F to 158 F relative humidity at 77 F max 95 the air conditioner should always be stored according to the installation position Returning the unit To avoid transport damage the unit should be returned...

Страница 20: ...Version Nr 1 9 14 03 2022 Doc No 9987251082USL 20 20 75 Circuit Drive North Kingstown RI 02852 United States Tel 401 294 6960...

Отзывы: