background image

Version Nr. 1-11 - 05.10.2022

Doc. No. 9985409576

21 / 24

15. Trouble shooting

Failure

Condition

Cause

Solution

Unit
doesn't
cool

 Internal fan does not work

 Power not connected.

 Verify power supply

 Internal fan works, external fan
 and compressor don't work

 Enclosure temperature is below
 setting temperature (St1)

 Verify values of parameter
 "St1"

 Door switch contact is open

 Verify door switch

 Controller doesn't work

 Replace controller

 Internal fan works, external fan
 and  compressor don't work.
 Display shows alternating OFF 
 and temperature

 The sequence of the phases
 inside the power supply
 connector is incorrect

 Change phases inside power 
 supply connector

 External and internal fan work,
 compressor does not work

 Compressor motor electrical
 failure

 Have compressor replaced  
 by qualified service technician

 Capacitor for compressor failed  Replace capacitor

 Compressor works, external fan
 doesn't work

 External fan needs to be
 replaced

 Replace external fan

Enclosure
temperature 
too high

 Compressor and fans (external
 and internal) work all the time

 Cooling unit undersized

 Enclosure needs a cooling
 unit with with higher capacity

 Compressor and external fan 
 work in alternating mode
 (ON / OFF)

 Thermal compressor protector
 triggered 

 Verify if ambient temperature
 is too high,clean condenser

 Refrigerant leakage

 Contact dealer/service center

Excessive 
condensate

 Enclosure door open

 Ambient air gets into the  
 enclosure

 Ensure door is closed, add
 a door switch and connect
 it to controller

 Enclosure door closed

 Enclosure IP protection class 
 is below IP54

 Seal all openings of the
 enclosure

 Damaged or misplaced sealing
 strip

 Repair sealing strip
 accordingly

16. Maintenance & Cleaning

Always switch power supply off before starting any maintenance on the unit.
Wait for 5 minutes for electrical components to discharge.

The cooling unit is generally maintenance free and can be operated without filters in most environments. 

If the ambient air is extremely dusty, we recommend installing filter mats (see accessories). These should be
cleaned or replaced at regular intervals. Oily or greasy filter mats should be replaced immediately. Do not use a
steam jet or high pressure to clean the filter mats. Do not wring out the filter mats.If the ambient air is
extremely oily, we recommend the use of metal filters (see accessories). They can be cleaned with standard
cleaning agents and reused. In addition the unit should have regular functional tests (approx. every 2,000 hours
depending on the grade of ambient pollution).

Note: The use of filter mats / metal filters reduces the cooling capacity of the unit..

Disposal
The cooling unit contains R134a refrigerant and small quantities of lubricating oil. Replacement, repairs and
final disposal must be done according to the regulations of each country for these substances.

Содержание 85409576

Страница 1: ...gs 4 5 Functional principle 5 6 Technical data 6 7 Performance graph 7 8 Mounting 8 9 Mounting Principle 11 10 Cut out dimensions 12 11 Electrical connection 13 12 Controller 15 13 Wiring diagram 19 1...

Страница 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage Indicates e...

Страница 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid saf...

Страница 4: ...does not come into contact with the ambient air which may well be dirty or polluted Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclosures...

Страница 5: ...refrigerant thus taking it to high pressure and high temperature and pushes it through the condenser where it is cooled by ambient air thus passing from the gas to the liquid state At the liquid state...

Страница 6: ...825 cfm Enclosure 441 706 cfm Mounting Wall mounted recessed Housing Material Mild steel powder coated Dimension H x W x D 1550 x 455 x 270 mm Weight 136 lbs Voltage Frequency 380 415 V 50 Hz 3 400 4...

Страница 7: ...Version Nr 1 11 05 10 2022 Doc No 9985409576 7 24 7 Performance graph...

Страница 8: ...internal and external are not obstructed It must also be ensured in accordance with UL that the air outlet is not blowing air directly at an equipment operator Should this be the case a barrier or du...

Страница 9: ...Nr 1 11 05 10 2022 Doc No 9985409576 9 24 Cold air outlet duct When using a cold air outlet duct please follow the steps below Filter installation If you install replace a lter please follow the step...

Страница 10: ...s The integrated condensate evaporation of the cooling unit releases the condensate to the environment If condensate formation is too great additional condensate can drip into an over ow trough which...

Страница 11: ...after installation Use only the supplied mounting hardware Tighten Screws to 4 5 Nm Ensure the mounting surface does not warp after assembly and reinforce it if necessary 1 M6 screws 2 M6 toothed wash...

Страница 12: ...Version Nr 1 11 05 10 2022 Doc No 9985409576 12 24 10 Cut out dimensions...

Страница 13: ...oller Setting temperature units C F low temperature alarm door contact logic section for more information c68 0 default ON if closed Door contact terminals bridged or NC door switch connected contact...

Страница 14: ...10 2022 Doc No 9985409576 14 24 Connect unit Connect the cooling device according to the instructions below The cable cross section must correspond to the required power for the current consumption bu...

Страница 15: ...ung aktiv 4 Relais Umgebungsl fter aktiv Alarm Blinkt wenn Alarm aktiv ist Heizmodus Zeigt an da das Ger t im Heizmodus ist K hlmodus Zeigt an da das Ger t im K hlmodus ist TEST Testmodus l uft Kann n...

Страница 16: ...raturalarm Grenzwert voreingestellt 10 C 14 F P26 f r Hochtemperaturalarm Grenzwert voreingestellt 55 C 131 F c68 f r T rkontakt NO NC Logik nderung 0 ON wenn geschlossen 1 ON wenn o en Steuerung Firm...

Страница 17: ...werden diese nacheinander angezeigt Fehlercode Beschreibung L sung OFF T r o en Schaltschrankt re schlie en ggfs T rkontaktschalter berpr fen Wenn kein T rkontaktschalter vorhanden und c68 0 T rkonta...

Страница 18: ...wird erscheint der Firmware Versionscode f r 2 Sekunden F r die Reinigung des Displays bitte nicht thylalkohol Kohlenwassersto e Benzin Ammoniak oder Derivate verwenden Es empfehlen sich Neutralreini...

Страница 19: ...Version Nr 1 11 05 10 2022 Doc No 9985409576 19 24 13 Wiring diagram Anschlu stecker 1 L1 2 3 N 4 PE Signalstecker 1 Alarm NO 2 Alarm COM 3 Alarm NC 4 T rkontakt 5 T rkontakt...

Страница 20: ...be protected with a MCB Type D or K Upon connection the internal fan will start working If the temperature inside the enclosure is higher than the set value of the controller both the compressor and e...

Страница 21: ...erant leakage Contact dealer service center Excessive condensate Enclosure door open Ambient air gets into the enclosure Ensure door is closed add a door switch and connect it to controller Enclosure...

Страница 22: ...temperature range 40 F to 158 F Relative humidity at 77 F max 95 The cooling unit should always be stored according to the installation position Returning the unit To avoid transport damage the unit...

Страница 23: ...Einstein Str 3 HF09 10 Wilerstrasse 16 B rnthal 1 Rep O ce 75 Circuit Drive 105 Lewis Road Hal Far Industrial Estate North Kingstown Wantirna South 42477 Radevormwald Birzebbuga BBG 3000 4563 Gerla ng...

Страница 24: ...05 10 2022 Doc No 9985409576 24 24 info de seifertsystems com info seifertsystems com info ch seifertsystems com info at seifertsystem com info seifertsystems com info us seifertsystems com info seife...

Отзывы: