background image

Version Nr. 1-11 - 05.10.2022

Doc. No. 9985409576

13 / 24

11. Electrical connection

Caution, risk of death

Unconnected and / or faulty protective conductor systems can lead to dangerous voltages and electric shocks
which can cause serious accidents.

Work on electrical connections may only be carried out by trained electrical engineers.

Door Switch
The unit can be switched ON and OFF via a door contact switch. When delivered the door contact terminals are
bridged on the female connector. To connect the door contact switch remove the bridge and connect door
contact switch. The contact must be closed when the cabinet door is closed.

It is possible to change the logic of the door switch (controller firmware rev. 1.2 or higher). This can be set by
changing the value of parameter c68. Refer to the table below and section Controller: Setting temperature units
(°C / °F), low temperature alarm, door contact logic section 
for more information.

c68 = 0 (default)

ON if closed - Door contact terminals bridged, or NC door switch connected
(contact must be closed when cabinet door is closed)

c68 = 1

ON if open - Remove bridge, or NO door switch connected
(contact must be open when cabinet door is closed)

Alarm Contacts
Alarm contacts rated according to:

EN60730-1 8(4)A N.O., 6(4)A N.C., 2(2)A N.O./ N.C. @ 250Vac 100000 cycles
UL 873

8A resistive 2FLA 12LRA, pilot duty C300 @ 250Vac 30000 cycles

These contacts are not suitable for fluorescent loads (neon lights, etc.) that use starters (ballasts) with phase
shifting capacitors. Fluorescent lamps with electronic controllers or without phase shifting capacitors can be
used, depending on the operating limits specified for each type of relay.

SCCR
Refer to UL508A Supplement SB and Seifert Systems’ document 

Short Circuit Current Rating (SCCR)

 on methods

how to modify the available short circuit current within a circuit in the panel.

Содержание 85409576

Страница 1: ...gs 4 5 Functional principle 5 6 Technical data 6 7 Performance graph 7 8 Mounting 8 9 Mounting Principle 11 10 Cut out dimensions 12 11 Electrical connection 13 12 Controller 15 13 Wiring diagram 19 1...

Страница 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage Indicates e...

Страница 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid saf...

Страница 4: ...does not come into contact with the ambient air which may well be dirty or polluted Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclosures...

Страница 5: ...refrigerant thus taking it to high pressure and high temperature and pushes it through the condenser where it is cooled by ambient air thus passing from the gas to the liquid state At the liquid state...

Страница 6: ...825 cfm Enclosure 441 706 cfm Mounting Wall mounted recessed Housing Material Mild steel powder coated Dimension H x W x D 1550 x 455 x 270 mm Weight 136 lbs Voltage Frequency 380 415 V 50 Hz 3 400 4...

Страница 7: ...Version Nr 1 11 05 10 2022 Doc No 9985409576 7 24 7 Performance graph...

Страница 8: ...internal and external are not obstructed It must also be ensured in accordance with UL that the air outlet is not blowing air directly at an equipment operator Should this be the case a barrier or du...

Страница 9: ...Nr 1 11 05 10 2022 Doc No 9985409576 9 24 Cold air outlet duct When using a cold air outlet duct please follow the steps below Filter installation If you install replace a lter please follow the step...

Страница 10: ...s The integrated condensate evaporation of the cooling unit releases the condensate to the environment If condensate formation is too great additional condensate can drip into an over ow trough which...

Страница 11: ...after installation Use only the supplied mounting hardware Tighten Screws to 4 5 Nm Ensure the mounting surface does not warp after assembly and reinforce it if necessary 1 M6 screws 2 M6 toothed wash...

Страница 12: ...Version Nr 1 11 05 10 2022 Doc No 9985409576 12 24 10 Cut out dimensions...

Страница 13: ...oller Setting temperature units C F low temperature alarm door contact logic section for more information c68 0 default ON if closed Door contact terminals bridged or NC door switch connected contact...

Страница 14: ...10 2022 Doc No 9985409576 14 24 Connect unit Connect the cooling device according to the instructions below The cable cross section must correspond to the required power for the current consumption bu...

Страница 15: ...ung aktiv 4 Relais Umgebungsl fter aktiv Alarm Blinkt wenn Alarm aktiv ist Heizmodus Zeigt an da das Ger t im Heizmodus ist K hlmodus Zeigt an da das Ger t im K hlmodus ist TEST Testmodus l uft Kann n...

Страница 16: ...raturalarm Grenzwert voreingestellt 10 C 14 F P26 f r Hochtemperaturalarm Grenzwert voreingestellt 55 C 131 F c68 f r T rkontakt NO NC Logik nderung 0 ON wenn geschlossen 1 ON wenn o en Steuerung Firm...

Страница 17: ...werden diese nacheinander angezeigt Fehlercode Beschreibung L sung OFF T r o en Schaltschrankt re schlie en ggfs T rkontaktschalter berpr fen Wenn kein T rkontaktschalter vorhanden und c68 0 T rkonta...

Страница 18: ...wird erscheint der Firmware Versionscode f r 2 Sekunden F r die Reinigung des Displays bitte nicht thylalkohol Kohlenwassersto e Benzin Ammoniak oder Derivate verwenden Es empfehlen sich Neutralreini...

Страница 19: ...Version Nr 1 11 05 10 2022 Doc No 9985409576 19 24 13 Wiring diagram Anschlu stecker 1 L1 2 3 N 4 PE Signalstecker 1 Alarm NO 2 Alarm COM 3 Alarm NC 4 T rkontakt 5 T rkontakt...

Страница 20: ...be protected with a MCB Type D or K Upon connection the internal fan will start working If the temperature inside the enclosure is higher than the set value of the controller both the compressor and e...

Страница 21: ...erant leakage Contact dealer service center Excessive condensate Enclosure door open Ambient air gets into the enclosure Ensure door is closed add a door switch and connect it to controller Enclosure...

Страница 22: ...temperature range 40 F to 158 F Relative humidity at 77 F max 95 The cooling unit should always be stored according to the installation position Returning the unit To avoid transport damage the unit...

Страница 23: ...Einstein Str 3 HF09 10 Wilerstrasse 16 B rnthal 1 Rep O ce 75 Circuit Drive 105 Lewis Road Hal Far Industrial Estate North Kingstown Wantirna South 42477 Radevormwald Birzebbuga BBG 3000 4563 Gerla ng...

Страница 24: ...05 10 2022 Doc No 9985409576 24 24 info de seifertsystems com info seifertsystems com info ch seifertsystems com info at seifertsystem com info seifertsystems com info us seifertsystems com info seife...

Отзывы:

Похожие инструкции для 85409576