4 / 17

4. Settings

Air - water heat exchangers are intended as complementary accessories to large industrial equipment which
include a motor-operated fan or blower together with a cooling heat exchanger. These may also include an
electric heater. The fan or blower is intended to recirculate air and allow heat exchange. The heat exchanger is
designed for chilled water or anti-freeze/corrosion inhibitor mixed water from a separate source.
The cooling function may be controlled by an on-board or remote controller or thermostat, a thermostatically
controlled valve or an electrically controlled valve. Heating function, when installed is provided by an electrical
heating element. The unit seals the cabinet which ensures that the clean air inside does not come into contact
with the ambient air which may well be dirty or polluted. The unit is fit for purpose within the rated/declared
ambient conditions (e.g. dusty and oily air or high air temperatures between 34°F and 162°F), also indicating
the rated allowable ingress and environment.

Water quality
To ensure the maximum lifetime of an air-water heat exchangers, it is important to supply cooling water in
conformity with the VGB Cooling Water Guidelines (VGB-R 455 P). The cooling water used must be soft enough
to avoid scale deposits, but should not be too soft as this would corrode the heat exchanger. Where the cooling
water is cooled for reuse, part of the water has to be changed with fresh water to prevent the concentration of
hardness and salt content which makes the water more corrosive.
The main impurities and possible methods of eliminating them are given in the table below:

Pollution of the water

Method of elimination

Mechanical impurities (dp > 2mm)

Filtration of the water

Excessive hardness

Softening of the water by ion
exchange

Moderate content of mechanical impurities
and hardness formers

Addition of dispersants or stabilisers

Moderate content of chemical impurities

Addition of passivators and inhibitors

Biological impurities (bacteria and algae)

Addition of biocides

When the water is re-cooled, it is recommended that the water condition is maintained as close as possible to
the following list of hydrological data:

Hydrological data

 

 

pH-values

7 - 8.5

 

Carbonate hardness

>3 <8 

°dH

Free carbon dioxide

8 - 15

mg/dm³

Associated carbon dioxide

8 - 15

mg/dm³

Aggressive carbon dioxide

0

mg/dm³

Sulphides

free

mg/dm³

Oxygen

< 10

mg/dm³

Chloride ions

< 50

mg/dm³

Sulphate ions

< 250

mg/dm³

Nitrates and nitrites

< 10

mg/dm³

COB

< 7

mg/dm³

Ammonia

< 5

mg/dm³

Iron

< 0.2

mg/dm³

Manganese

< 0.2

mg/dm³

Conductivity

< 2200

µS/cm

Solid residue from evaporation

< 500

mg/dm³

Potassium manganate consumption < 25

mg/dm³

Suspended matter

< 3

mg/dm³

(part flow cleaning recommended)  > 3 < 15 mg/dm³
(continuous cleaning)

> 15

mg/dm³

Содержание 750621B001

Страница 1: ...afety instructions 3 4 Settings 4 5 Functional principle 5 6 Technical data 6 7 Performance graph 7 8 Mounting 8 9 Mounting Principle 9 10 Cut out dimensions 10 11 Dimensions H x W x D 11 12 Controller 12 13 Wiring diagram 13 14 Taking into operation 14 15 Maintenance Cleaning 15 16 Maintenance 15 17 Transport Storage 16 ...

Страница 2: ... instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the following High electric voltage Indicates electric shock danger Important safety instruction Indicates instructions for safe maintenance and operation of the unit Attention Indicates possible burns from hot components Attention Indicates poss...

Страница 3: ...ad with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid safety regulations One can find dangerous voltages above 50 V AC or above 100 V DC Behind the control cabinet doors On the power supply in the unit housing The unit has to be operated according to the ty...

Страница 4: ...t be soft enough to avoid scale deposits but should not be too soft as this would corrode the heat exchanger Where the cooling water is cooled for reuse part of the water has to be changed with fresh water to prevent the concentration of hardness and salt content which makes the water more corrosive The main impurities and possible methods of eliminating them are given in the table below Pollution...

Страница 5: ...ous circulation of the air in the cabinet This circulation prevents hot spots within the control cabinet During this process the coolant heats up and is returned to the coolant supply system at an increased temperature In order to save operating costs and in the interests of environmental protection the water temperature can be reduced by re cooling systems or cold water sets so that it can be reu...

Страница 6: ...ial Mild steel powder coated Dimension H x W x D 600 x 250 x 127 37 90 mm Weight 8 5 Kg Voltage Frequency 380 415 V 50 Hz 2 400 460 V 60 Hz 2 Starting current 1 0 A Max current 0 25 A Max power 35 W Pressure water circuit 10 bar Water connection Rp 3 8 Innengewinde mit optionalen Anschlüssen für Rohrinnendurchmesser von 10 mm Fuse 1 A T Connection 5 polige Anschlussklemme für Signale 4 polige Ansc...

Страница 7: ...Version Nr 1 3 09 11 2022 Doc No 99750621B001 7 17 7 Performance graph ...

Страница 8: ...ealed control cabinet will result in an increased level of condensation The control cabinet should have a minimum of IP54 protection in accordance with IEC 60 529 Cooling medium connection There are two pipe connection points in the bottom or in the top of the unit to connect the coolant supply The pipe connectors have a G3 8 or G1 2 female thread depending on version Before connecting the coolant...

Страница 9: ...Version Nr 1 3 09 11 2022 Doc No 99750621B001 9 17 9 Mounting Principle ...

Страница 10: ...Version Nr 1 3 09 11 2022 Doc No 99750621B001 10 17 10 Cut out dimensions ...

Страница 11: ...Version Nr 1 3 09 11 2022 Doc No 99750621B001 11 17 11 Dimensions H x W x D ...

Страница 12: ...ie geschützten Parameter Sobald Sie auf die Parameterliste zugreifen wird wieder PS angezeigt Drücken Sie die Tasten UP oder DOWN um durch die verschiedenen Parameter zu blättern Drücken Sie SET um bei Bedarf den gespeicherten Wert des ausgewählten Parameters anzuzeigen Drücken Sie auf UP DOWN um den Parameterwert bei Bedarf zu ändern Drücken Sie SET um den aktuell angezeigten Wert zu speichern We...

Страница 13: ...Version Nr 1 3 09 11 2022 Doc No 99750621B001 13 17 13 Wiring diagram Zuleitung PE L3 L2 L1 Signalsteckverbinder Türkontakt T2 Türkontakt T1 Alarmkontakt P2 Alarmkontakt P1 ...

Страница 14: ...tons to scroll the numbers until displaying 22 default password to access the parameters press the SET button to confirm the password 3 Use the UP and DOWN buttons to scroll the parameters The LED corresponding to the category of parameters will be on 4 Press SET to display the value associated with the parameter 5 Increase or decrease the value using the UP or DOWN button respectively 6 Press SET ...

Страница 15: ... fan by loosening the 4 fastening screws To detach the fan from the fan support loosen a further 4 screws and the fan connecting cable When connecting the new fan take care that the correct polarity is maintained 2 Controller replacement Before replacing the controller isolate the equipment from the power supply pull out mains plug or connecting cable Detach the controller from its support by uncl...

Страница 16: ... to the unit through incorrect transport Please ensure that all liquid has been removed prior any transport To avoid transport damage the unit should be returned in the original packing or in a packing case and must be strapped to a pallet If the unit cannot be returned in the original packing please ensure that A space of at least 1 18 inch must be maintained at all points between the unit and th...

Страница 17: ...Estate North Kingstown Wantirna South 42477 Radevormwald Birzebbuga BBG 3000 4563 Gerlafingen 4901 Ottnang 26100 Cremona RI 02852 3152 Victoria Germany Malta Switzerland Austria Italy USA Australia Tel 49 2195 68994 0 Tel 356 2220 7000 Tel 41 32 675 35 51 Tel 43 7676 20712 0 Tel 39 349 259 4524 Tel 1 401 294 6960 Tel 61 3 98 01 19 06 info de seifertsystems com info seifertsystems com info ch seifer...

Отзывы: