The cooling unit is intended to be used as a complementary accessory to larger industrial equipment. The unit
is used where heat needs to be dissipated from electrical control cabinets or similar enclosures in order to
protect heat sensitive components. It is not intended for household use.
The unit has two completely separate air circuits which ensure that the clean cabinet air does not come into
contact with the ambient air which may well be dirty or polluted.

Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical
enclosures into the ambient air and at the same time reduce the cabinet internal temperature to below that of
the ambient air. The unit can function without problems in extreme ambient conditions (e.g. dusty and oily air)
with a standard operating temperature ranging between 10°C and 55°C. Units can be ordered with an
additional electrical cabinet heater. For the cooling capacities and evironmental ratings please refer to the type
plate data.

Содержание 43302101

Страница 1: ...ional principle 6 6 Technical data 7 7 Performance graph 8 8 Mounting 9 9 Mounting Principle 10 10 Cut Out Dimension 11 11 Dimension H x W x D 12 12 Electrical Connection 13 13 Controller 14 14 Wiring Diagram 15 15 Taking into Operation 16 16 Trouble Shooting 16 17 Maintenance Cleaning 16 18 Transport Storage 17 19 Parts supplied Spare parts Accessories 18 ...

Страница 2: ...dissipation of heat from control cabinets and enclosures stationary not moving in order to protect temperature sensitive components in an industrial environment To meet the conditions of use all the information and instructions in the instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the followin...

Страница 3: ...units based on the information diagrams or descriptions contained in this manual No liability can be accepted for damage and production caused by Disregarding the instruction manual Operating error Inappropriate work on or with the unit The use of non specified spare parts and accessories Unauthorised modifications or changes to the unit by the user or his personnel The supplier is only liable for e...

Страница 4: ...y regulations One can find dangerous voltages above 50 V AC or above 100 V DC Behind the control cabinet doors On the power supply in the unit housing The unit has to be operated according to the type plate and the wiring diagram and must be protected externally from overloading and electrical faults via suitable protective devices Danger through incorrect work on the unit The unit can only be inst...

Страница 5: ...t air does not come into contact with the ambient air which may well be dirty or polluted Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclosures into the ambient air and at the same time reduce the cabinet internal temperature to below that of the ambient air The unit can function without problems in extreme ambient conditions e g dusty ...

Страница 6: ...he capillary pipe being a much lower pressure the refrigerant arrived to the evaporator where it absorbs the necessary heat to change from liquid to gas state The gas is then drawn back into the compressor completing the cycle Condensation management In environments with humidity and low internal enclosure temperatures condensation may form on the evaporator coil Standard cooling units 43XXX0XXX h...

Страница 7: ...50 1200 m h Cabinet air circuit 860 1200 m h Mounting Wall mounted Housing Material Mild steel powder coated Dimensions A x B x C D E 1 230 x 500 x 340 mm Weight 72 5 kg Cut out dimensions 1 130 x 430 mm Voltage Frequency 380 415 V 50 Hz 3 400 460 V 60 Hz 3 UL Voltage Frequency 400 460 V 60 Hz 3 Current L35L35 2 1 A 50 Hz 2 3 A 60 Hz Starting current 7 6 A 8 1 A Max current 3 3 A 3 5 A Nominal pow...

Страница 8: ...Version No 1 3 11 06 2022 Doc No 9943302101 8 18 7 Performance graph ...

Страница 9: ...he case a barrier or duct shall be provided to redirect the airflow Cooling unit enclosure air suction hole must be installed in the highest possible point When installing the unit on a door ensure it can take the weight Before drilling the enclosure ensure the fixing elements and couplings will not interfere with the equipment inside the enclosure itself Disconnect power before starting any work in...

Страница 10: ...No 9943302101 10 18 9 Mounting Principle Do not use within the first 15 minutes after installation 1 M6 screws 2 M6 flat washers 3 M6 toothed washers 4 Cabinet 5 Sealing tape 6 Cooling unit 7 Lifting hook Fig 1 Recessed Fig 2 External ...

Страница 11: ...Version No 1 3 11 06 2022 Doc No 9943302101 11 18 10 Cut Out Dimension ...

Страница 12: ...Version No 1 3 11 06 2022 Doc No 9943302101 12 18 11 Dimension H x W x D ...

Страница 13: ...t terminals are bridged on the female connector To connect the door contact switch remove the bridge and connect door contact switch The contact must be closed when the cabinet door is closed SCCR Refer to UL508A Supplement SB and Seifert Systems document Short Circuit Current Rating SCCR on methods how to modify the available short circuit current within a circuit in the panel ...

Страница 14: ...Press Set to save the new setting To change the heating set point St2 units with internal heater only 1 Press Set till St1 appears on the display and release the button 2 Press again Set till St2 appears on the display 3 Press the Up Down buttons to adjust the temperature 4 Press set to save the new setting Important Note when changing settings ensure that St2 5K St1 The unit also has a potential ...

Страница 15: ...aporator PSM Phase sequence module AT Autotransformer EB External blower IB Internal blower PC 9 pole connector CC 7 core cable CC2 6 core cable CC3 8 core cable PC2 4 pole connector PC CONNECTIONS 1 L1 2 L2 3 L3 4 Earth 5 400V TR 6 Common 7 460V TR PC2 CONNECTIONS 1 Alarm P1 2 Alarm P2 3 Door contact T1 4 Door contact T2 For 400V supply bridge contacts 5 6 for 460V supply bridge contacts 6 7 ...

Страница 16: ... power supply connector is incorrect Change phases inside power supply connector Unit doesn t cool External and internal fan work compressor does not work Compressor motor electrical failure Have compressor replaced by qualified service technician Capacitor for compressor failed Replace capacitor Compressor works external fan doesn t work External fan needs to be replaced Replace external fan Enclo...

Страница 17: ...tions which meet the following conditions temperature range 40 C to 70 C Relative humidity at 25 C max 95 Returning the unit To avoid transport damage the unit should be returned in the original packing or in a packing case and must be strapped to a pallet If the unit cannot be returned in the original packing please ensure that A space of at least 30 mm must be maintained at all points between th...

Страница 18: ...Ltd Seifert Systems AG Seifert Systems GmbH Seifert Systems Ltd Seifert Systems Inc Seifert Systems Pty Ltd Albert Einstein Str 3 HF09 10 Wilerstrasse 16 Bärnthal 1 Rep Office 75 Circuit Drive 105 Lewis Road Hal Far Industrial Estate North Kingstown Wantirna South 42477 Radevormwald Birzebbuga BBG 3000 4563 Gerlafingen 4901 Ottnang 26100 Cremona RI 02852 3152 Victoria Germany Malta Switzerland Austri...

Отзывы:

Похожие инструкции для 43302101