background image

Version No. 1-2 - 04.06.2021

Doc. No. 9942691001

13 / 17

12. Taking into Operation

Attention
The unit can be damaged by lack of lubricant.

To ensure that the compressor is adequately lubricated the oil, which has been displaced during transport, must
be allowed to flow back into it. The unit must therefore be allowed to stand for at least 30 min. after mounting
before being connected to the mains and taken into operation.
The unit / system must be protected with a MCB Type D or K. 
The unit is controlled in relation to the cabinet internal temperature. A temperature sensor continuously
measures the temperature of the air which is drawn into the unit from the cabinet. The required cabinet temp.
can be set on the cabinet temperature potentiometer on the PC-board. The temperature adjustment range is
between 20°C (left-hand stop) and 50°C (right-hand stop). The potentiometer is factory pre-set at 35°C.

To adjust the cabinet internal temperature please proceed as follows:

Remove the fixing screws from the unit cover and the earth wire from inside it.
Lift off the cover.
Remove the PCB cover.
Using a screwdriver turn the cabinet temperature potentiometer on the PC-board slightly to the right
(higher) or to the left (lower)
Close the unit in the prescribed manner.

Check that the new adjusted values meet the necessary requirements. If necessary repeat the procedure. The
compressor together with the ambient radial fan are switched ON or OFF, depending on the cabinet internal air
temperature.  Here the minimum shut-down time corresponds with the start-up delay. The cooling mode will
switch on as soon the desired temperature is reached. The start-up delay is depending on the unit size 3 or 7
min. The cooling mode will switch off as soon as the desired temperature is undercut by 3K (hysteresis) (KG
4266854 has a 5K hysteresis) and / or when the max. running time of 3 min. is reached.

When the test button is pressed the compressor and the ambient fan will run for 120-240 sec. regardless of the
cabinet temperature. During this period the green LED on the PC-board will blink twice as fast as normal. If the
test button is pressed during the 120-240 sec. test-run, the unit will return to its normal operational mode. The
test-run should only be repeated after a minimum compressor shut-down time of 10 min.

NOTE: ​When the unit is taken into operation for the first time, a start-up delay of the cooling circuit for ca. 4-7
min. independent of temperature setting and actual cabinet temperature will take place.

Содержание 42691001

Страница 1: ...3 4 Settings 4 5 Functional Principle 4 6 Technical Data 5 7 Mounting 6 8 Condensate management 8 9 Mounting Principle 9 10 Electrical Connection 10 11 Wiring Diagram 12 12 Taking into Operation 13 13...

Страница 2: ...ons in the instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage...

Страница 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid saf...

Страница 4: ...vironmental ratings please refer to the type plate data 5 Functional Principle The cooling unit for enclosures works on the basis of a refrigeration circuit consisting of four main components compress...

Страница 5: ...low Volume System Unimpeded Ambient air circuit 250 650 m h Cabinet air circuit 125 250 m h Mounting Wall mounted Recessed Housing Material Mild steel powder coated Dimension A x B x C D E 600 x 320 x...

Страница 6: ...irit level that the cabinet is in a horizontal position The max deviation from the vertical or horizontal is 3 degrees Air apertures To provide adequate air circulation and avoid temperature layers fr...

Страница 7: ...the surface of the cabinet and remove the mounting template Stick the self adhesive unit seals on the outer surface of the cabinet for externally mounting and on the inner surface of the cabinet for...

Страница 8: ...The condensation drain pipe should be attached as required e g in conditions of high humidity To install an oel cleaning drain 2 pipe please follow below steps Remove the plastic stopper from in the b...

Страница 9: ...4 06 2021 Doc No 9942691001 9 17 9 Mounting Principle Do not use within the rst 15 minutes after installation 1 Mounting gasket 2 Mounting clip 3 M6 slotted set screw 4 Washer 5 Lock nut Fig 1 Recesse...

Страница 10: ...external components it must be ensured that the wiring and connections are double insulated and safe against touch and protected from unauthorized and or accidental external contact Ensure that the co...

Страница 11: ...minals T1 T2 Connect the door contact switch to terminals T1 T2 The contact must be closed when the cabinet door is closed SCCR Refer to UL508A Supplement SB and Seifert Systems document Short Circuit...

Страница 12: ...Version No 1 2 04 06 2021 Doc No 9942691001 12 17 11 Wiring Diagram...

Страница 13: ...on the PC board slightly to the right higher or to the left lower Close the unit in the prescribed manner Check that the new adjusted values meet the necessary requirements If necessary repeat the pr...

Страница 14: ...Install the unit at a di erent place The ambient temperature must be within the stated operating temperature range The control cabinet is not sealed properly The control cabinet needs re sealing Fan o...

Страница 15: ...ction The connections 1 2 and 3 4 are not low voltage 50V Regularly check the condenser pro le for dirt tests approx every 2 000 hours depending on the grade of ambient pollution Should the condenser...

Страница 16: ...fan xing screws Connect the fan cable to the PC board and replace the board if necessary Dispose the old fan according to the environmental laws and regulations 16 Transport Storage Malfunction due t...

Страница 17: ...rt Systems Ltd Seifert Systems Inc Seifert Systems Pty Ltd Albert Einstein Str 3 HF09 10 Wilerstrasse 16 B rnthal 1 Rep O ce 75 Circuit Drive 105 Lewis Road Hal Far Industrial Estate North Kingstown W...

Отзывы:

Похожие инструкции для 42691001