background image

Version No. 1-4 - 28.04.2021

Doc. No. 9942681001

4 / 18

4. Settings

The cooling unit is intended to be used as a complementary accessory to larger industrial equipment,
and is used where heat needs to be dissipated from electrical control cabinets or similar enclosures in order to
protect heat sensitive components.  It is not intended for household use. The unit has two completely separate
air circuits which ensure that the clean cabinet air does not come into contact with the ambient air which may
well be dirty or polluted. The cooling unit can dissipate large quantities of heat from electrical enclosures into
the ambient air and at the same time reduce the internal temperature to below that of the ambient air. The unit
works without problems in extreme ambient conditions (e.g. dusty and oily air). The operating temperature
range is b20°C and +55°C. Units can be ordered with an additional electrical cabinet heater. For
the cooling capacities and evironmental ratings please refer to the type plate data.

5. Functional Principle

The cooling unit for enclosures works on the basis of a refrigeration circuit consisting of four main
components: compressor, evaporator, condenser and expansion device. 
The circuit is hermetically sealed and R134a refrigerant circulates inside it (R134a is chlorine free and has an
Ozone Destruction Potential [ODP] of 0 and a Global Warming Potential [GWP] of 1430). The compressor
compresses the refrigerant (thus taking it to high pressure and high temperature), and pushes it through the
condenser, where it is cooled by ambient air thus passing from the gas to the liquid state. At the liquid state it
then passes through the capillary pipe being a much lower pressure the refrigerant arrives to the evaporator
where it absorbs the necessary heat to change from liquid to gas state. The gas is then drawn back into the
compressor completing the cycle.

1   Air intake cabinet side   6   Air intake ambient side
2   Radial fan cabinet side   7   Radial fan ambient side
3   Evaporator

  8   Condenser

4   Air outlet cabinet side   9   Air outlet ambient side
5   Compressor

  10   Filter dryer

     

  11   Expansion device

 

Содержание 42681001

Страница 1: ...unctional Principle 4 6 Technical Data 5 7 Mounting 6 8 Condensate management 8 9 Mounting Principle 9 10 Electrical Connection 10 11 Controller Layout Description 12 12 Wiring Diagram 13 13 Taking in...

Страница 2: ...ons in the instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage...

Страница 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid saf...

Страница 4: ...vironmental ratings please refer to the type plate data 5 Functional Principle The cooling unit for enclosures works on the basis of a refrigeration circuit consisting of four main components compress...

Страница 5: ...rature Range 10 C 50 C Air Flow Volume System Unimpeded Ambient air circuit 200 450 m h Cabinet air circuit 125 250 m h Mounting Wall mounted Recessed Housing Material Mild steel powder coated Dimensi...

Страница 6: ...irit level that the cabinet is in a horizontal position The max deviation from the vertical or horizontal is 3 degrees Air apertures To provide adequate air circulation and avoid temperature layers fr...

Страница 7: ...the surface of the cabinet and remove the mounting template Stick the self adhesive unit seals on the outer surface of the cabinet for externally mounting and on the inner surface of the cabinet for...

Страница 8: ...The condensation drain pipe should be attached as required e g in conditions of high humidity To install an oel cleaning drain 2 pipe please follow below steps Remove the plastic stopper from in the b...

Страница 9: ...8 04 2021 Doc No 9942681001 9 18 9 Mounting Principle Do not use within the rst 15 minutes after installation 1 Mounting gasket 2 Mounting clip 3 M6 slotted set screw 4 Washer 5 Lock nut Fig 1 Recesse...

Страница 10: ...s it must be ensured that the wiring and connections are double insulated and safe against touch and protected from unauthorized and or accidental external contact Ensure that the correct polarity is...

Страница 11: ...ct the door contact switch to terminals T1 T2 The contact must be closed when the cabinet door is closed SCCR Refer to UL508A Supplement SB and Seifert Systems document Short Circuit Current Rating SC...

Страница 12: ...Doc No 9942681001 12 18 11 Controller Layout Description C1 2 3 Fan capacitors C Connection terminals M Microcontroller Alarm Potentiometer alarm temperature Temp Potentiometer cabinet temperature T T...

Страница 13: ...re potentiometer 1 L1 Live 120 V 2 N Neutral PE Earth 4 T1 Door contact bridged with T2 5 T2 Door contact bridged with T1 Normal with power ON Alarm with power ON 6 P1 Alarm contact 7 P2 Alarm contact...

Страница 14: ...on the PC board slightly to the right higher or to the left lower Close the unit in the prescribed manner Check that the new adjusted values meet the necessary requirements If necessary repeat the pr...

Страница 15: ...Install the unit at a di erent place The ambient temperature must be within the stated operating temperature range The control cabinet is not sealed properly The control cabinet needs re sealing Fan o...

Страница 16: ...ction The connections 1 2 and 3 4 are not low voltage 50V Regularly check the condenser pro le for dirt tests approx every 2 000 hours depending on the grade of ambient pollution Should the condenser...

Страница 17: ...fan xing screws Connect the fan cable to the PC board and replace the board if necessary Dispose the old fan according to the environmental laws and regulations 17 Transport Storage Malfunction due t...

Страница 18: ...ystems Ltd Seifert Systems Inc Seifert Systems Pty Ltd Albert Einstein Str 3 HF09 10 Wilerstrasse 16 B rnthal 1 Rep O ce 75 Circuit Drive 105 Lewis Road Hal Far Industrial Estate North Kingstown Wanti...

Отзывы:

Похожие инструкции для 42681001