Seifert 2300110 Скачать руководство пользователя страница 7

Version No. 1-4 - 02.06.2021

Doc. No. 992300110

7 / 13

7. Mounting

The power supply rating on unit rating plate must comply with mains rating.

 

 

Always disconnect the power supply before opening the unit.

Seifert heat exchangers have an extremely compact design and construction, giving them the advantage of
occupying very little space. In addition, the RK-2114 A/AM, RK-2114 A/AM 632 and RK-2116 A/AM models can be
mounted externally or internally, as required.
To achieve a good seal between the control cabinet and the heat exchanger, the unit's mounting surface on the
control cabinet may need to be reinforced. The air intake and outlet must not be obstructed by equipment
inside the control cabinet, so that the air is mixed thoroughly and thermal stratification is avoided.
For the heat exchanger to work perfectly, the cabinet must be completely sealed from its surroundings. An
imperfectly sealed control cabinet will result in an increased level of condensation. The control cabinet should
have a minimum of IP54 protection, in accordance with IEC 60 529.

Use of the mounting template
The mounting template enables the unit to be installed quickly. For mounting the template should be attached
to the wall of the cabinet and the holes for the fixing screws should be drilled in the wall of the cabinet in the
marked positions.

Cooling medium connection
There are two pipe connection points on the bottom (RK-2114, RK-2116, RK-2140) or in the side (RK-2124) of
the unit to connect the refrigerant supply. The piping used for the supply must have an internal diameter of 10
mm or 13 mm depending on the model. The pipe connectors have a ¼” thread (1/2" RK 2125948 / RK 21259500
/ RK 2149) and can be replaced with other connectors for larger or smaller pipe diameters. Before connecting
the coolant circuit, note the flow direction of the coolant medium. Next to the pipe connectors, the letters “E”
and “A” are visible on the unit.

E

coolant intake

A

coolant outflow

To empty the unit connect the water inlet pipe to a compressed air supply and route the water outlet pipe to a
location where the water can be drained. Set the thermostatic head inside the unit to a set-point lower than
ambient temperature to ensure it opens and slowly open the compressed air supply till all the water in the heat
exchanger is flushed out. Ensure that the pressure of the system is below the rated pressure of the unit and
fitting.

Содержание 2300110

Страница 1: ...l Regulations 2 3 Safety Instructions 3 4 Settings 4 5 Functional Principle 5 6 Technical Data 6 7 Mounting 7 8 Mounting Principle 9 9 Wiring Diagram 10 10 Taking into Operation 11 11 Maintenance Clea...

Страница 2: ...ns in the instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage I...

Страница 3: ...with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid safe...

Страница 4: ...55 P The cooling water used must be soft enough to avoid scale deposits but should not be too soft as this would corrode the heat exchanger Where the cooling water is cooled for reuse part of the wate...

Страница 5: ...s constantly providing continuous circulation of the air in the cabinet This circulation prevents hot spots within the control cabinet During this process the coolant heats up and is returned to the c...

Страница 6: ...peded 85 240 m h Mounting Wall mounted recessed Housing Material Mild steel powder coated Dimension A x B x C D E 303 x 153 x 84 mm Weight 4 5 kg Voltage Frequency 120 V 60 Hz Starting Current 0 74 A...

Страница 7: ...g template enables the unit to be installed quickly For mounting the template should be attached to the wall of the cabinet and the holes for the xing screws should be drilled in the wall of the cabin...

Страница 8: ...ion drain pipe should be attached as required e g in conditions of high humidity To install an oel cleaning drain 2 pipe please follow below steps Remove the plastic stopper from in the base of the un...

Страница 9: ...Version No 1 4 02 06 2021 Doc No 992300110 9 13 8 Mounting Principle 1 Bolt 2 Toothed washer 3 Washer 4 Enclosure 5 Mounting gasket...

Страница 10: ...Version No 1 4 02 06 2021 Doc No 992300110 10 13 9 Wiring Diagram M1 Radial fan X3 3 pin connector L1 Live N Neutral PE Earth protection...

Страница 11: ...the unit To set the ow rate Q turn the thermostatic head Set the indicator position to the required cabinet temperature The work s setting of the water ow regulator is 35 C The adjustment range is 20...

Страница 12: ...ure If no button is pressed for 60 sec all changes made to the parameters temporarily saved in the RAM will be cancelled and the previous settings restored The cooling unit manufacturer is in no way l...

Страница 13: ...ned in the original packing or in a packing case and must be strapped to a pallet If the unit cannot be returned in the original packing please ensure that A space of at least 30 mm must be maintained...

Отзывы: