ExP[2] . Trigger Signal
[Protection Para / ExP[2]]
If: Device Variant/Inputs = Without Inputs
• “-”
•
If: Device Variant/Inputs = Without Inputs
• “-”
•
If: Device Variant/Inputs = Ext. Trip
• “-”
•
If: Device Variant/Inputs = Ext. Trip, Ext. Reset
• “-”
•
If: Device Variant/Inputs = Configurable
• “-”
•
If: Device Variant/Inputs = Configurable Inputs
• “-”, Prot . DI 1, Prot . DI 2
•
P.1
Assign the trigger signal that will make the »ExP« module start (pickup).
ExP[2] . Condition
[Protection Para / ExP[2]]
“-”
“-”, I> . Pickup, I>> . Pickup, I>>> . Pickup, Ipeak> . Pickup, Prot .
Pickup
P.1
Assign a signal that must be active in additon to the external signal for making the »ExP« module start (pickup). (If
no signal has been assigned here then the »ExP« module always picks up as soon as the external signal becomes
active.)
ExP[2] . ExBlo
[Protection Para / ExP[2]]
“-”
“-” . . . Prot . Pos OFF
P.1
External blocking of the module if the state of the assigned signal is true.
7.18.3
ExP[2]: Input States
ExP[2] . ExBlo-I
[Operation / Status Display / ExP[2]]
Module input state: External blocking
ExP[2] . Trigger Signal-I
[Operation / Status Display / ExP[2]]
State of the module input: External trigger signal
72
WIC1
WIC1-1.0-EN-REF
7 Protection Parameter
7.18.3 ExP[2]: Input States