7.17
ExP[1] – External Protection - Module
7.17.1
ExP[1]: Device Planning Parameters
ExP[1] . Mode
[Device planning / Projected Elements]
use
“-”, use
P.1
External Protection - Module, general operation mode
ExP[1] . Definition
[Device planning / Definition]
Trip
Trip, Alarm
P.1
External Protection - Module: If set to “Alarm”: The function operates as a supervision function, i.e. a fault generates
neither alarm nor trip, but an »Alarm« signal gets issued instead. If set to “Trip”: The function operates as a
protection function, i.e. trips the breaker in case of a fault.
7.17.2
ExP[1]: Settings
ExP[1] . Function
[Protection Para / ExP[1]]
Active
Inactive, Active
P.1
Permanent activation or deactivation of module/stage.
ExP[1] . t
[Protection Para / ExP[1]]
0.00s
0.00s . . . 60.00s
P.1
Time delay for trip or alarm
68
WIC1
WIC1-1.0-EN-REF
7 Protection Parameter
7.17 ExP[1] – External Protection - Module