SEG Electronics GmbH
Manual MRG3
80
DOK-TD-MRG3, Rev. D
7.8.4 Earth fault supervision
Setting range
Step
(Range)
Tolerance
I
E
>
Warn or trip of I
E
> element
trip; warn
I
E
>
1...200 % (EXIT)
0.1
(1...5)
0.2
(5...10)
0.5
(10...20)
1
(20...50)
2
(50...100)
5
(100...200)
3% of the set value
or.
0.3% I
N
tI
E
>
0.04 - 300 s (EXIT)
(definite time)
0.02
(0.06...1.0)
0.05
(1.0...2.0)
0.1
(2.0...5.0)
0.2
(5.0...8.5)
0.5
(10...20)
1,0
(20...50)
2.0
(50...100)
5.0
(100...200)
10.0
(200...300)
3% or
20 ms
I
E
_Char
Normal Inverse
Typ “A”
Very Inverse
Typ “B”
Extremely Inverse Typ “C”
RI - Inverse
Long Time Inverse
RXIDG-Kennlinie
NINV
VINV
EINV
RINV
LINV
RXID
0,05 - 10 (EXIT)
0.05
– 1.0 (EXIT) only RXIDG
(inverse time)
0.01
(0.05...0.5)
0.02
(0.5...1.0)
0.05
(1.0...2.0)
0.1
(2.0...5.0)
0.2
(5.0...10.0)
3% related to the measured
current value and
20ms re-
spectively
(see EN 60255-3)
tI
E
>
Reset
Reset Mode for tripping times
0s; 60s
I
E
>>
1...400 %
(EXIT)
0,1
(1...5)
0,2
(5...10)
0,5
(10...20)
1
(20...50)
2
(50...100)
5
(100...200)
10
(200...400)
3% of the set value
tIE>>
0.04...300 s (EXIT)
0.02
(0.06...0.5)
0.05
(0.5...2.0)
0.1
(2.0...5.0)
0.2
(5.0...10)
0.5
(10...20)
1.0
(20...50)
2.0
(50...100)
5.0
(100...200)
10.0
(200...300)
3% or
20 ms
Table 7.4: Earth fault supervision
* Tripping time in forward direction (tripping range)
** Tripping time in backward direction (blocking range), see chapter 4.7.3