10.7 Wall Mounting
Install wall mounting brackets at the height shown in the
layout drawing provided by the estimator. Space wall
mounting brackets and hangers as indicated by
dimensions d, e and f (u-tube) in the relevant layout
overview drawing for your heater. For linear heaters
, for double linear heaters
and for U-tube heaters
10.7.1 Hardware Installation
The wall mounting brackets must be attached to a
suitable wall through all mounting holes. Screw sizes less
than M8 (5/16") may not be used. In order for the wall
Figure 27: U-Tube (Horizontal)
SECTION 10: O
PTIONAL
H
EATER
A
CCESSORIES
mounting brackets to adequately carry the weight of the
heater, it must be installed with best building practice.
Model
Quantity of Wall
Mounting
Brackets
Model
Quantity of Wall
Mounting
Brackets
ATH15UT
2
ATH15ST
3
ATH20UT
3
ATH20ST
4
ATH25UT
3
ATH25ST
4
ATH30UT
3
ATH30ST
5
ATH35UT
3
ATH35ST
5
ATH40UT
3
ATH40ST
5
ATH45UT
4
ATH45ST
6
ATH50UT
4
ATH50ST
6