-6-
12A4A2-00007E-8
4-5
Environmental Specification
Item
Specifications
Ambient operating temperature
(Inside cabinet and display side)
0
℃
to 55
℃
Ambient storage temperature
-10
℃
to +60
℃
Ambient operating humidity
10%RH to 85%RH
(non-condensing.
Wet-bulb temperature is 39
℃
or less)
Ambient storage humidity
10%RH to 85%RH
(non-condensing.
Wet-bulb temperature is 39
℃
or less)
Dust
Prohibited
Corrosive Gas
Corrosive gas Prohibited
Environmen
t
Pollution Degree 2, Indoor use
Pressure resistance
800hPa to 1114hPa (Altitude up to 2000m)
Vibration resistance
IEC61131-2(JIS B 3502) compliant
5Hz to 9Hz Single amplitude 3.5mm
9Hz to 150Hz Fixed acceleration 9.8m/s
2
X,Y,Z directions for 10times(100min.)
4-6
Installation Specification
Item
Specifications
Grounding
Grounding resistance of 100Ω, 2mm
2
[0.0062inch
2
] or thicker wire,
or your country’s applicable standard.
Structure
Protection Structure: IP65 *
1
(Front side only when mounted to panel)
Installation : Panel mounting
Cooling
Natural cooling
Weight
Approx. 700g (unit only)
External Dimensions
192 (W) mm x 137 (H) mm x 36 (D) mm
Panel Cutout Dimensions
183.5
+
0.5/-0
(W) mm x 128.5
+
0.5/-0
(H) mm
*1.
Protection structure of the front part of the unit when installed to a panel. Although it has been
tested under conditions equivalent to the standards shown in the specification, use under all
environments are not guaranteed. Especially for oils defined in the test, in cases where EMG7
is prolonged to vaporized oils or cutting fluids with especially low viscosity, oil might enter the
front area through an area where touch screen has lifted and may need special
measurements. Please check the installation environment prior to use. Also, gaskets that
have been used for a long time or have once been installed to panels, the original level of the
protection cannot be guaranteed. To maintain the stable, original protection level, we
recommend replacing the installation gasket regularly.