GC1100
SEDEMAC
Page | 30
Level 0
Level 1 (On
screen)
Level 2 (On screen) *
Parameters (On screen)
Monitoring
(CHARGE ALT
MON)
Charging Alternator Fail
Threshold
(FAIL THRESHOLD)
0.0 – 35.0 V
Charging Alternator Fail Delay
(FAIL DELAY)
5 – 60 sec
Preheat
(PREHEAT)
Preheat Timer
(PREHEAT TIMER)
1 – 900 sec
Engine Temperature
(ENG TEMPERATURE)
Disable/Enable
Engine Temperature Threshold
(ENG TEMP THRESH)
10 – 300 ̊C
Maintenance
(MAINTENANCE)
Maintenance
(MAINT
ALARM)
Action
(ACTION)
Notification/Warning
Due At Engine Hours
(DUE AT ENGINE HOURS)
10 – 65000 hour
Alarm Due
Date
(ALARM DUE
DATE)
DD/MM/YYYY
Miscellaneous
Settings
(MISC
SETTINGS)
PASSWORD 1
####
0 – 9 for each digit
PASSWORD 2
####
0 – 9 for each digit
(RESET
COUNTERS)
(MAINS)
(RUN TIME)
(In numbers)
MAINS kWh
(In kWh)
MAINS kVAh
(In kVAh)
MAINS kVArh
(In kVArh)
(GENSET)
(RUN TIME)
(In hours)
(NO OF STARTS)
(In numbers)
(NO OF TRIPS)
(In numbers)
ENG kWh
(In kWh)
ENG kVAh
(In kVAh)
ENG kVArh
(In kVArh)
7.2
Digital Input Sources Selection
Following table gives a brief overview of selection criteria for digital input sources
Table 21: Digital input sources selection
#
Source (On screen)
1
Not Used
2
User Configured
3
Low Fuel Level Switch (Low Fuel LVL Switch)
4
Lube Oil Pressure Switch (Low Lube Oil Press Switch)
5
High Engine Temp Switch