GC1100
SEDEMAC
Page | 9
Communication Ports
Following table gives a brief overview of communication ports
Table 16: Communication ports
USB
USB 2.0 Type B used for connection to PC running SEDEMAC Smart
config.
RS485 Serial Port
Half Duplex
Max Baud Rate 115200
Data connection 2 wire
Termination resistor of 120Ω is provided between output pin A & B
Common-mode operating range and bus-pin fault protection upto ±70V
Maximum distance of line is 1200m
Controller's terminal
number for RS485
15, 16
CAN
Baud rate used is 250 kbps
Packet size used is 8 bytes
Termination resistor of 120Ω is provided
Controller's terminal
number for CAN
13, 14