EPI-BUS devices
Mounting and installation, Technical Description, T 811 086 en e
79 / 128
8.6.4
Instructions for opening and mounting the B5-EPI-FPS-S
BRAND
FLERA LARM
SLÄCKANLÄGGNING
AKTIVERAD
BRANDVENTILATION
AKTIVERAD
STYRUTGÄNG
AKTIVERAD
LARMSÄNDARE
AKTIVERAD
DRIFT
TILL
FRÅN
MANÖVER
ÅTERSTÄLLNING
LARMDON TYST
1
1
1
1
2
3
3
3
Fig. 101 Mounting B5-EPI-FPS-S
To detach the housing front from the housing rear, press the housing inwards on the right or left side
(1)
. Remove the hous-
ing front by pulling it upwards
(2)
. Using a tapered bit, drill the holes for the required cable inlets in the top, bottom or rear of
the housing and attach the enclosed cable bushings
(3).
Insert the cables and screw the housing rear onto the mounting surface (four screws and dowels included in the scope of
supply). The two recesses for cable ties in the housing rear can be used for strain relief. Connect the wires on the terminal
block and set the EPI bus address. Position the housing front on the housing rear and push in until it snaps into place.