Main control units
Mounting and installation, Technical Description, T 811 086 en e
29 / 128
5.3
Connection of monitored inputs and outputs
The X10 connector plug on the B6-BCB13 and B6-BCB12 main control units is for connecting the transmission unit (main
detector) and alarm unit (sirens) for loads between 16
Ω and 1 kΩ. The interface includes two 1.5 A control outputs moni-
tored for short-circuit and wire breakage and two monitored inputs. The OM1 output has a feedback input for external trigger
confirmation.
Notice
Due to the fusing of the internal peripheral voltage (27 V) with quick-action 4 A, the maximum total output cur-
rent of all simultaneously actuated monitored outputs must not exceed a continuous current of 4 A per control
panel.
X10 connector plug
Pin
Designation
Function
Fig. 33 B6-BCB, input and output interface
1
OM1+
+24V
2
OM1-
GND
3
OM1CF+/-
Feedback input
4
OM2+
+24V
5
OM2-
GND
6
IM1+
Input 1
7
IM1-
GND
8
IM2+-
Input 2
9
IM2-
GND
5.3.1
Technical data
Monitored outputs OM1 and OM2
Output voltage:
22 V min., 24 V typical, 28 V max.
Output current:
max. 1.3 A (TUS max. 0.1 A)
OM modes of operation:
monitored output with range 1 to 3 or TUS (only OM1),
planning with software; see table for values
Feedback input:
feedback from MDLF
Input current
3.1 mA
Polarity
feedback contact can switch to plus and minus
Output
Mode of opera-
tion
Load range
Output current
Quiescent cur-
rent
Short-circuit current
Line resistance
OM1
Range 1
160-
1000 Ω
max. 1.3 A
1 mA
typically 1.75 A
max. 50 Ω
Range 2
57-
375 Ω
max. 1.3 A
3 mA
typically 1.75 A
max. 20 Ω
Range 3
20-
80 Ω
max. 1.3 A
13 mA
typically 1.75 A
max. 5 Ω
TUS
max. 220 Ω
max. 0.1 A
15 mA
typically 0.137 A
max. 20 Ω
OM2
Range 1
160-
1000 Ω
max. 1.3 A
1 mA
typically 1.75 A
max. 50 Ω
Range 2
57-
375 Ω
max. 1.3 A
3 mA
typically 1.75 A
max. 20 Ω
Range 3
20-
75 Ω
max. 1.3 A
13 mA
typically 1.75 A
max. 5 Ω
Monitored inputs IM1 and IM2
Purpose:
polling galvanically isolated contacts or key safes and isolating facilities
Monitoring voltage:
typically 24 V
Monitoring current:
typically 3.1 mA
Short-circuit current:
typically 3.63 mA
Termination resistance:
220 Ω
Initiating resistance:
220 Ω
Line resistance:
50 Ω max.