SecuriLine eXtended
102 / 128
Mounting and installation, Technical Description, T 811 086 en e
10.3.3
Connection of MCP 535x and MCP 545x manual call points
L1
L2
GND
GND
SHLD
SHLD
4
3
2
1
5
7
6 8
L
2
L
1
G
N
D
G
N
D
S
H
L
D
S
H
L
D
MCP 535X
Fig. 126 MCP 535x connection
MCP 545X
MCP 545N
S
H
L
D
G
N
D
L
1
G
N
D
S
H
L
D
L
2
1
2
3
4
5
6
7
8
SHLD
L1
GND
GND
L2
SHLD
Fig. 127 MCP 545x connection
10.3.4
Connection of BX-AIM advanced input module
The BX-AIM advanced input module can be used as monitored input for polling potential-free contacts or as detection zone
for connecting collective detectors. Among other things, it can be used to connect intrinsically safe detectors (Ex-i) with in-
termediate switching of a
Zener
barrier. An output for a repeat signal is also available.
Further information about the BX-AIM can be found in the data sheet T 811 100.
Collective detector and monitored input
Extinguishing input in accordance with VdS
BX-AIM
GND
C
SHLD
P-
SHLD
GND
L
L1
L Ex
1
1
L2
P+
X2
X1
19k1
560 R
L1
L2
G
N
D
G
N
D
SH
LD
S
H
LD
Indicator
_
+
Fig. 128 BX-AIM, collective detector and monitored in-
put
BX-AIM
GND
C
SHLD
P-
SHLD
GND
L
L1
L Ex
1
1
L2
P+
X2
X1
Extinguisching
control panel
3k3
680 R
L1
L2
G
N
D
G
N
D
SH
LD
SH
LD
Fig. 129 BX-AIM, extinguishing input compliant with VdS
MMD130 Ex-i in Ex area
GND
SHLD
SHLD
GND
L1
L2
X2
C
P-
L
L Ex
1
P+
X1
BX-AIM
1
L1
L2
G
N
D
G
N
D
S
H
LD
S
H
LD
+
-
5
1
8
4
Local earthing safety barrier,
additional equipotential bonding 10 mm to FACP earthing
2
+
+
-
-
Safety barrier
Z787F
Ex-area
Max. 4 USB 501-7 Ex-i detector bases
Last detector
19k1
Fig. 130 BX-AIM, MMD130 Ex-i in Ex area