FEATURES 

TCR-T-KT electrical actuators are intended for motorising ¼ turn valves with a torque of 50 or 80 Nm. 

Double  proportional  control  function  4-20mA  +  closing  manoeuvre  provided  by  a  super-capacitor.

  With  a  compact 

construction and plastic housing, they are especially well suited for motorising small size ball valves. The actuator has 
many advanced control functions which can be set from the screen. IP67 leak-tightness: to be used indoors and, possibly, 
outdoors under a shelter. Manual control with a key. 

 

AVAILABLE MODELS

 

Supply voltages: 230V AC, 24V AC/DC. 
Control: 4-20 mA, 0-20 mA, 2-10V, 0-10V. 
   

          

                                  

LIMITS OF USE 

 

 
 
 
 

MECHANICAL FEATURES 

 

 

 
 
 
 

 

 

Actuator 

TCR 05T-KT32 

TCR 11T-KT32 

Torques (Nm) 

50 

80 

Voltage 

24V AC - DC 

95-265V AC-DC 

24V AC - DC 

95-265V AC-DC 

Adjustment signal 

4-20 mA, 0-20 mA, 2-10V, 0-10V 

Feedback signal 

4-20 mA, 0-20 mA, 2-10V, 0-10V 

Manoeuvring time (s) 

12 

12 

10 

10 

ISO 5211: 

F05/F07 - star 14 

F05/F07 - star 17 

 

ELECTRICAL FEATURES 

 

Actuator 

TCR 05T-KT32 

TCR 11T-KT32 

Motor protection 

Thermal switch 

Anti-condensation 

integrated 

Electrical connection  

PE M20 + 1.5m cable 

2 x PE M14 

 
 
 

Actuator 

TCR 05T-KT32 

TCR 11T-KT32 

Voltage 

24V AC - DC 

95-265V AC-DC 

24V AC - DC 

95-265V AC-DC 

Power (W) 

40 

40 

100 

100 

Current (A) 

1,8 

0,18 

2,5 

0,3 - 0,6 

Fuse protection (A) 

10 

IP Code 

IP 67 

Ambient  temperature 

- 20°C / +60°C 

Service factor 

S4-50%  

Gear box 

treated steel pinions 

Torques 

50 - 110 Nm 

Angle of rotation 

90° +/- 2° 

Declutching 

without 

Override control 

By key 

IP 

67 

ISO 

9001

 

 

Содержание TCR 05T-KT32

Страница 1: ...doors and possibly outdoors under a shelter Manual control with a key AVAILABLE MODELS Supply voltages 230V AC 24V AC DC Control 4 20 mA 0 20 mA 2 10V 0 10V LIMITS OF USE MECHANICAL FEATURES Actuator TCR 05T KT32 TCR 11T KT32 Torques Nm 50 80 Voltage 24V AC DC 95 265V AC DC 24V AC DC 95 265V AC DC Adjustment signal 4 20 mA 0 20 mA 2 10V 0 10V Feedback signal 4 20 mA 0 20 mA 2 10V 0 10V Manoeuvring...

Страница 2: ...ctoriel fr Email sectoriel sectoriel fr Pages 2 9 Ref FT2419B ENG Rev 01 Date 02 2020 CONSTRUCTION TCR 05T KT32 DIMENSIONS mm TCR 05T KT32 No Name Material No Name Material 1 Casing lid Plastic ABS 7 1 3 LCD display OLED 2 Position indicator Polycarbonate plastic 8 Rating plate PVC 3 Screw x 6 Ansi 304 9 Packing gland Nylon 4 Backup control stem Ansi 304 10 Hex key Steel 5 Gasket NBR 11 Key suppor...

Страница 3: ...ectoriel sectoriel fr Pages 3 9 Ref FT2419B ENG Rev 01 Date 02 2020 CONSTRUCTION TCR 11T KT32 DIMENSIONS mm TCR 11T KT32 No Name Material No Name Material 1 Casing lid Plastic ABS 7 1 3 LCD display OLED 2 Position indicator Polycarbonate plastic 8 Rating plate PVC 3 Screw x 6 Ansi 304 9 Key support Plastic ABS 4 Backup control stem Ansi 304 10 Hex key Steel 5 Gasket NBR 11 X 2Packing gland Nylon 6...

Страница 4: ...G DIAGRAM DESCRIPTION OF THE 1 3 LCD SCREEN 1 3 LCD angle without any blind spot strong luminosity automatic switching to the economy saving mode at the end of 5 minutes The control screen displays the set value and the of opening of the valve BU Neutral Blue RD Closing control Red Y G Earth Yellow Green BK Alarm return information Black GR Alarm return information Green PL 0 10V and 2 10V control...

Страница 5: ...e desired position is reached Press the K3 button to manoeuvre anti clockwise The screen displays the of opening Release when the desired position is reached PARAMETER SETTING MENU OF THE ACTUATOR The following functions can have their parameters set from the menu accessible on the screen STEP TITLE FUNCTION AND VALUES 1 Standby screen If the actuator did not receive any signal in the last 5 minut...

Страница 6: ...the band the lower the accuracy the narrower the band the more oscillating the system can be Setting range 0 1 to 9 9 Setting by default 0 8 8 Hysteresis adjustment This parameter setting is a prerequisite for the next YES adjustment is possible NO no adjustment is possible value by default 9 Hysteresis value If the previous parameter is YES it is possible to set the hysteresis value between 0 1 a...

Страница 7: ...5 Setting the speed for the stroke This setting is used for setting a of the actuator stroke during which it will slow down before reaching the setpoint value position Range 1 20 Value by default 10 16 Braking time In order to increase the stability of the motor the motor will slow down after a short time before reaching its setpoint value position During current use this function is not useful Ra...

Страница 8: ...mA output signal this function is used to adjust it If the number is increased the current is higher If the number is decreased the current is lower Range 191_1000_A Value by default 909_A 21 Power supply position by default Setting the position of the valve in the event of a power cut This manoeuvre will be carried out if the capacitor is sufficiently charged Possible values KEEP unchanged positi...

Страница 9: ...fault ON 27 Exiting the menu Press K3 to exit the menu The system will switch back in the automatic checking mode TROUBLESHOOTING Defect met Cause of defect Method of solving Inactive actuator Non connected electrical grid Connect to the electrical grid Wrong voltage Check the actuator s voltage Motor overheating Check the torque on the valve Faulty connection Check the connection to the terminal ...