9. ANOMALIES AND SOLUTIONS
Any current or past anomaly can be viewed using the parameters 0.01 and 0.02, or using the parameter 9.00
for errors concerning only the self-learning process of the shaft system VEN01 (i.e. with encoder, see
paragraph
). Each alarm is identified by a numeric code, the meaning of which is shown in the following
tables.
9.1. Legend
Alarm type
•
“A”
: alarm that causes out of service, with automatic reset (you have just to remove the causes)
•
“
M
”
: alarm that causes out of service, with manual reset (you have to remove the causes and then
to reset the error with the parameter 0.03, or with SW1 push-button if enabled by parameter 0.35.0)
•
Without any indication: alarm that not causes out of service
9.2. Alarm codes displayed at parameters 0.01 and 0.02
Generic alarms
A
LARM
CODE
TYPE
DESCRIPTION
001
M
Excessive motor working time without car movement (see timer
002
M
Excessive motor working time at low speed (see timer
003
A
Excessive motor temperature (detected by thermal sensor RT)
004
A
Out of service caused by
(out of service with car stopped and levelled at a floor)
005
M
Excessive number of re-levelling operations (see parameter
)
006
M
Failure to open main contactors (KM)
007
M
Failure to open upward contactor (KS) / star-delta contactor (KT)
008
M
Failure to open downward contactor (KD) / soft starting resistor exclusion contactor
009
A
Phase loss or wrong phases rotation detected by RCF01 board (see also
)
010
A
No voltage on safety chain point 1 (see also
)
011
M/A
Overrun (a limit switch SEC, SEC1, SEC2 was actuated). See also
.
012
A
An emergency stop is actuated (SAF, SMA1, SMA2, SMAQ), or safety gear is engaged (SPT)
013
Overload (SP1/SCS)
014
A
Safety photocell activated out of the door unlocking zone, for cars without doors (SFS1, SFS2, SFS3). See also
015
A
Failure to close the main contactors (KM)
016
A
Failure to close the upward contactor (KS) / star-delta contactor (KT)
017
A
Failure to close the downward contactor (KD)
018
A
Reserved
019
A
Safety circuit CS4 is active during departure preliminaries (with relay AV excited)
020
A
Safety circuit (CS4) not active with door opening commands enabled.
021
Failure to close of car/landing door safety contacts (SBP01, SPC1, SPC2, SPC3)
022
A
The state of the activating device of the UCM protection means (see
) is inconsistent with the car movement
command, at departure. See also timer
.
023
A
The state of the activating device of the UCM protection means (see
) is inconsistent with the car movement
command, at landing. See also timer
.
024
A
Excessive switching frequency of main contactor KM (greater than the value set with parameter
)
025
A
Failure to open of the relays that commands the electrical interlocks. See also
.