123-567 Rev. A

 

 

agent, in its proper concentration, will remain in the enclosed compartment and 
not be ingested or reduced by the running machinery.   
 
Immediately upon agent discharge, the ESRS PS1 closed loop circuit opens, 
activating the alarm and de-energizing all the relays.  De-energizing the relays will 
change the state of the internal contacts and shut down all the machinery 
connected to the ESRS unit.  The PS1 LED on the Unit and the DISCHARGE LED on 
the Display Panel illuminate.  The activated alarm can be silenced by pressing the 

SILENCE

 button on the ESRS unit or on the connected Display Panel.   

After a discharge or loss in cylinder pressure resulting in an opened PS1 loop, 

simultaneously pressing the 

SILENCE

 and the 

 

buttons will put

 

the ESRS into 

override enabling all the machinery connected to the ESRS to restart.  The ESRS can 
only be properly reset after the discharged agent cylinder has been 
refilled/replaced and then the 

SHUTDOWN RESET

 buttons pressed to put the unit 

back into the standby mode.  In the standby mode, only the POWER green LED on 
the ESRS and the Display Panel will remain on.   
 
If there is a High-Temperature, Low-Pressure or an Auxiliary Discharge sensor 
switch connected to the PS2 terminals when the sensor switch opens, the alarm 
activates and both the PS2 LED on the unit and the Second Zone LED on the Display 
Panel illuminate.  There will be no change to the relays

 state.  The activated PS2 

circuit alarm can be silenced by pressing the 

SILENCE

 button on the ESRS box or on 

the connected Display Panel.  Reset the unit after the PS2 circuit condition has been 
remedied by pressing the 

SHUTDOWN RESET

 buttons.  The unit is now in standby 

mode.     
 

3

 

ESRS INSTALLATION 

CAUTION: Make sure all power sources are shut down prior to installation. 

Install the ESRS unit in a conveniently accessible and well-ventilated location.  The 
ESRS should not be exposed to environmental temperatures (in excess of 
54

o

C/130

o

F) for an extended period.  This will affect the service life of the unit and 

may cause premature failure.   

3.1

 

Installation Location  

x

 

It is important that the ESRS unit is installed in a location that will not 
build up heat or be exposed to external heat sources. 

x

 

If installed in a box or cabinet, the enclosure should have sufficient 
ventilation. 

x

 

When installed in the engine room, the ESRS should be installed with 
sufficient protection from the hazards of that space, but must still have a 
way to dissipate heat and not be overheated by other sources. 

WARNING:  Do not install the ESRS Unit in a sealed enclosure. 

Содержание 131-440

Страница 1: ...ea Fire automatic and manual fire suppression systems Installation must be accomplished by or under the supervision of a qualified marine electrician who is familiar with American Boat and Yacht Council ABYC or other recognized and accepted marine standards and practices Caution Do not install this device in fuel storage compartments See the installation section of this manual for further details ...

Страница 2: ... 5 VIA RJ45 Socket Relays 5 VDC Form C Normally Open N O 20A Normally Closed N C 10A Connectors Wago 739 Max wire size 12AWG 2 5 mm Dimensions 7 29 W x 4 72 H x 2 37 D inch 185 2 W x 119 9 H x 60 2 D mm Weight 0 6 kg 1 3 lb Mounting Surface Compliant RoHS CE 1 1 Features x Fully automatic engine shutdown system x Shutdown override mode x Power On visual indication x Pressure Switch PS1 Visual and ...

Страница 3: ...ary Discharge sensor switch connected to the PS2 terminals when the sensor switch opens the alarm activates and both the PS2 LED on the unit and the Second Zone LED on the Display Panel illuminate There will be no change to the relays state The activated PS2 circuit alarm can be silenced by pressing the SILENCE button on the ESRS box or on the connected Display Panel Reset the unit after the PS2 c...

Страница 4: ...YC or equivalent international standard marine grade wire to connect all devices and power to the ESRS Connect the wire to the ESRS unit by pushing a 1 8 flathead screwdriver into the square opening on the top of the terminal block This opens the spring cage allowing a stripped wire to be installed into the round hole on the connector See Figure 1 Figure 1 Terminal Block Slot Properly ground all t...

Страница 5: ...ing the early warning alarm 3 3 1 3 Power Supply Terminals Main Supply Backup Supply and Generator x The ESRS Unit has 3 diode protected inputs but only one power source is needed to operate the ESRS and should be connected to and GND See Figure 2 o If available a backup power source should be connected to one of the additional power source inputs x Connect the ESRS unit to the power source s usin...

Страница 6: ...it connect all the supervisory pressure switches in series Connect the leading pressure switch wire to the Terminal marked 1 and the trailing wire of the last pressure switch to the Terminal marked 2 See Figure 2 x When connecting more than one Engineered System cylinder supervisory switch to the ESRS unit connect all the cylinder supervisory switches in series Connect the leading pressure switch ...

Страница 7: ...COM terminals are connected x The N O terminal is open 4 4 Relay 20 Second Reset Automatic reset timer functions are optional in the ESRS Please contact Sea Fire Marine for additional instruction regarding the setting of the relay 20 second reset timer 5 INSTALLATION CHECK 5 1 Check that all the machinery wires installed in the ESRS terminal blocks are correct and secure as described above and fro...

Страница 8: ...w Pressure High Temp or Aux Discharge LED on the Display Panel should illuminate The Relays should remain in the energized state 5 11 Reset the unit by closing the PS2 circuit and simultaneously press the SILENCE and the buttons 5 12 The Green power LED on the Display panel and the ESRS unit should be the only LEDs lit 5 13 Use one of the Display Panels in a multiple Display Panel chain to reset t...

Страница 9: ...an internal fault x Replace the ESRS unit 5 The SILENCE button on the ESRS unit does not silence the alarm x The ESRS SILENCE tactile switch on the ESRS unit has failed x Ensure that the tactile switch on the ESRS clicks when pushed in x The ESRS SILENCE tactile switch on the ESRS is fully depressed under the faceplate x Use a small pointed object to re center pin until it re seats above the facep...

Страница 10: ...OM CONFIGURATION DIAGRAMS NOTE THE 5A CIRCUIT BREAKER WITH ON OFF SWITCH ARE TO BE SUPPLIED BY CUSTOMER MANUAL AUTOMATIC FIRE SUPPRESSION SYSTEM UPON SYSTEM DISCHARGE SHUT DOWN ENGINE FORCED VENTILATION ELECTRICAL SYSTEMS FOR MANUAL OPERATION REMOVE PIN PULL HANDLE F I R E PN 136 XXX SMAC PULL CABLE 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH...

Страница 11: ...CUSTOMER 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH 5A CIRCUIT BREAKER WITH ON OFF SWITCH PN 124 LPS CYLINDER SUPERVISORY SWITCH SPST BLACK RED PN 124 969 OR PN 124 914 HORN STROBE P N 131 311 DISCHARGE PRESSURE SWITCH DPDT 4 NOTE THIS WIRING SCHEMATIC IS A REFERENCE EXAMPLE ONLY CUSTOMER SPECIFIC WIRING SCHEMATIC MAY APPLY PER CUSTOM CONFIGURATION DIAGRAMS ...

Страница 12: ... Europe LTD Baltimore Maryland or Hampshire www Sea Fire com United Kingdom Phone 1 410 687 5500 www Sea Fire co uk Fax 1 410 687 5503 ONE YEAR LIMITED WARRANTY We guarantee to the original retail purchaser of the Sea Fire Machinery Shutdown Restart System for a period of one 1 year after retail purchase against defective material and faulty workmanship Any Engine Interrupt System found to be defe...