3.3.
Manual Control Points
These switches are used to manually open and close actuators in a smoke control system. There is
a set lock-out period of 5 seconds between successive operations. The actuators open full stroke in
response to a transitory operation of the Manual Control Point. However, to prevent finger trapping
issues, the actuators only close whilst the Reset button on the Manual Control Point is maintained.
Note that the default Manual control point close mode can be changed by SE Controls to close
fully in response to a brief press of the reset button. This mode change is only recommended
where the activated vent is at least 2.5M above ground level to minimise finger trapping issues.
OS2 MCP
Part Number FCS00200016
OS2 Tamperproof MCP
Part Number FCS00200034
OS2 MCP Adaptor Plate
Part Number FCS00200017
All connections to the OS2 MCP are made via the connection PCB mounted
within the adapter plate assembly. (See diagram below.)
The connection PCB has 14 terminals, consisting of 2 pairs of 7 connections. For
OS2 products, it is only necessary to connect to 5 of these signals as follows:
MCP Terminal
OS2 Terminal
Description
24V
PER
24VDC power supply rail
from OS2 controller.
HLTY
FSL
Healthy indicator – from OS2 controller.
ACT
--
No connection required/
made for OS2 systems.
FLT
--
No connection required/
made for OS2 systems.
OPN
FSO
Open demand – from
Manual control point
CLS
FSC
Close demand – from
Manual control point
0V
0VP
0V power supply rail from
OS2 controller.
Note that each pair of connections are interconnected within the PCB assembly. The second set
of terminals may be used to daisy-chain multiple MCPs to one zone of the control panel.
24V
HLTY
ACT FLT OPN CLS
0V
24V HLTY ACT FLT OPN CLS
0V
CN1
CN2
FYS 1402 0018
CN3
HLTY = FSL
ACT =>
BEEP