6 Parameters List SV600 Series User Manual
44
6 Parameters List
If PP-00 is set to a non-zero number, parameter protection is enabled. You must enter the correct
user password to enter the menu.
To cancel the password protection function, enter with password and set PP-00 to 0.
Group P and Group A are standard function parameters. Group U includes the monitoring
function parameters.
The symbols in the parameter list table are described as follows:
"
☆
": The parameter can be modified when the frequency inveter in stop or running state.
"
★
": The parameter cannot be modified when the frequency inveter is in the running state.
"●": The parameter is the actually measured value and cannot be modified.
"*": The parameter is factory parameter and can be set only by the manufacturer.
P0 Group Basic Function Parameters
Function
code
Name
Setting range
Default
Property
P0-00
G/P type display
1: G type (constant torque load)
2: P type (fan and pump load)
1
★
P0-01
Motor 1 control mode
0: Speed sensorless vector control (SVC)
1: Reserved
2: V/F control
2
★
P0-02
Command source selection
0: Keyboard control (LED Off)
1: Terminal Control (LED on)
2: Communication Control (LED Flashing)
0
☆
P0-03
Main frequency source X
selection
0: Digital setting (preset by P0-08, not save when
power failure)
1: Digital setting (preset by P0-08, save when
power failure)
2: AI1
3: AI2
4: Potentiometer on the keyboard
5: PULSE pulse (HDI)
6: Multi-segment instruction
7: Simple PLC
8: PID
9: Communication setting
4
★
P0-04
Auxiliary frequency source
Y selection
Same as P0-03 (Main Frequency Source X
Selection)
0
★
P0-05
Auxiliary frequency source
Y-range selection
0: Relative to maximum frequency
1: Relative to frequency source X
0
☆
P0-06
Auxiliary frequency source
Y range
0% ~ 150%
100%
☆
P0-07
Frequency source method
selection
Units digit: frequency source selection
0: Main Frequency Source X
1: The calculation of X and Y (the relation is
determined by tens digit)
2: Switching between X(Main) and Y(Auxiliary)
00
☆