SV600 Series User Manual 7 Parameter Description
167
Group U0: Monitor Parameters
Group U0 is used to monitor the inverter's state. You can view the parameter values by using
keyboard, convenient for on-site commissioning, or from the upper device by means of
communication (address: 0x7000-0x7044).
U0-00 to U0-31 are the monitoring parameters in the running and stop state defined by P7-03 and
P7-04.
U0-00
Running frequency (Hz)
Display Range
0.00 ~ 320.00 Hz (P0-22=2)
0.0 ~ 3200.0 Hz (P0-22=1)
U0-01
Set frequency (Hz)
Display Range
U0-00 and U0-01 display the absolute value of theoretical running frequency and set frequency.
For the actual output frequency of the AC drive, see U0-19.
U0-02
Bus voltage (V)
Display Range
0.0 V ~ 3000.0 V
U0-03
Output voltage (V)
Display Range
0V ~ 1140V
U0-04
Output current (A)
Display Range
0.00A ~ 655.35 A (inverter power < =
55KW)
0.0A ~ 6553.5 A (inverter power >
55KW)
U0-05
Output
power
(KW)
Display Range
0 ~ 32767
U0-06
Output torque
Display Range
-200.0% ~ 200.0%
U0-07
DI input status
Display Range
0 ~ 32767
After the value is converted into a binary number, each bit corresponds to a DI. "1" indicates high
level signal, and "0" indicates low level signal. The corresponding relationship between bits and
DIs is described in the following table.
Bit0
Bit1
Bit2
Bit3
DI1
DI2
DI3
DI4
Bit4
Bit5
Bit6
Bit7
HDI
DI5
DI6
--
Bit8
Bit9
Bit10
Bit11
--
--
VDI1
VDI2
Bit12
Bit13
Bit14
Bit15
VDI3
VDI4
VDI5
--
U0-08
DO output status
Display Range
0 ~ 1023
After the value is converted into a binary number, each bit corresponds to a DO. "1" indicates
high level signal, and "0" indicates low level signal. The corresponding relationship between bits
and DOs is described in the following table.
Bit0
Bit1
Bit2
Bit3
Содержание SV600 Series
Страница 1: ...SV880 系列 Users Manual SV600 Series Ver 1 0 SHENZHEN SCOV ELECTRIC TECHNOLOGIES CO LTD ...
Страница 6: ......
Страница 24: ...3 Mechanical Installation SV600 Series User Manual 18 Fig d Fig e A 4Xd H H1 W B A 2 D A 2 W D H H1 ...
Страница 188: ...SV600 Series User Manual Appendix A Braking 182 Fig A 2 Applicable to inverter with external braking units ...