FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES
Water Supply:
The recommended water supply line is 3/8"
O.D. copper tubing, with a minimum operation
pressure of 20 PSIG, and a maximum of 120
PSIG. Connect to cold water using the male
flare connection at the back of the machine.
Install a shut off valve in an accessible space
between the ice maker and the water supply.
Drain System:
All drains are of the gravity type, and must
have a minimum of 1/4" fall per foot of
horizontal run. The drains must be installed to
conform to local plumbing codes. The use of a
vent at the machine and at the bin will allow
the system to drain properly. Use only rigid
tubing for drains; insulation of the bin drain is
recommended.
SHUT OFF
VALVE
FIELD
SUPPLIED
WATER FILTER
3/8" MALE FLARE
3/4" FPT
VENT THIS DRAIN
WATER INLET
BIN DRAIN
FLOOR DRAIN
NM1852RH
August 1992
Page 5