Settings
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
39
Settings Descriptions
!
WARNING:
Anytime an EZ setting is changed, review all the EZ settings before enabling the new settings. Pay close
attention in circumstances where a setting was once set to OFF or N and then later turned on (enabled) – other related
settings may need to be turned on, though may still be set to OFF or N.
Settings Groups 1 (Main) and 2 (Alternate) EZ Settings
No.
Setting
Default
Range
Incr.
1
Control Identifier
RECLOSER R1 0 - 9, A - Z, - , / , . , space
The
Control Identifier
setting contains the control installation designation (e.g., RECLOSER R1). This
identifier is listed at the top of event, history, meter, and status reports (see Table 2).
•
This setting may be up to 30 characters long.
•
This setting cannot be made via the front-panel interface.
No.
Setting
Default
Range
Incr.
2
Circuit Identifier
FEEDER 2101
0 - 9, A - Z, - , / , . , space
The
Circuit Identifier
setting contains the greater circuit or substation designation (e.g., FEEDER 2101).
This identifier is listed at the top of event, history, meter, and status reports (see Table 2).
•
This setting may be up to 30 characters long.
•
This setting cannot be made via the front-panel interface.
No.
Setting
Default
Range
Incr.
3 CT
Ratio
200.0
1.0-6000.0
0.1
The
CT Ratio
(current transformer [ct] ratio) setting programs the SEL-351P to operate with a recloser ct
ratio (e.g., for the common recloser ct ratio 200:1, the setting
CT Ratio
= 200.0 is made).
•
WARNING: The following settings change in accordance to the
CT Ratio
setting:
Min. trip - phase
(No. 5)
Min. trip - ground
(No. 6)
Min. trip - SEF
(No. 7)
No.
Setting
Default
Range
Incr.
4 PT
Ratio
100.0
1.0-10000.0
0.1
The
PT Ratio
setting is the potential transformer (pt) ratio.
•
For applications where single-phase 120 Vac power is the only voltage brought to the SEL-351P, the
pt ratio should still be entered, otherwise the SEL-351P voltage metering information will not be
accurate. Enter the effective power transformer ratio, relative to the 120 Vac secondary winding.
•
When calculating the PTR, verify that the unit for the power transformer primary voltage is Vac not
kVac.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......