Date Code 990430
Overcurrent, Voltage, Synchronism Check, and Frequency Elements
3-5
SEL-351P Manual Técnico
Directional Control Option
The phase instantaneous overcurrent element Relay Word bit outputs in Figure SECTION 3: .1
(50P1, 50P2, 50P3, and 50P4) are inputs into the phase instantaneous/definite-time overcurrent
element logic in Figure SECTION 3: .3.
Levels 1 through 4 in Figure SECTION 3: .3 have corresponding directional control options.
See Figure 4.21 in
Section 4: Loss-of-Potential, Load Encroachment, and Directional Element
Logic
for more information on this optional directional control. If the directional control enable
setting E32 is set:
E32 = N
then directional control is defeated, and the directional control inputs into all four phase
instantaneous/definite-time overcurrent element levels in Figure SECTION 3: .3 are asserted to
logical 1 continuously. Then only the corresponding SEL
OGIC
®
Control Equation torque control
settings have to be considered in the control of the phase instantaneous/definite-time overcurrent
elements.
For example, consider the Level 1 phase instantaneous/definite-time overcurrent elements
67P1/67P1T in Figure SECTION 3: .3. If the directional control enable setting E32 is set:
E32 = N
then the directional control input from Figure 4.21 (Level 1) is asserted to logical 1 continuously.
Then only the corresponding SEL
OGIC
Control Equation torque control setting 61P1TC has to be
considered in the control of the phase instantaneous/definite-time overcurrent elements
67P1/67P1T.
SEL
OGIC
Control Equation torque control settings are discussed next.
Torque Control
Levels 1 through 4 in Figure SECTION 3: .3 have corresponding SEL
OGIC
Control Equation
torque control settings 67P1TC through 67P4TC. SEL
OGIC
Control Equation torque control
settings cannot be set directly to logical 0. The following are torque control setting examples for
Level 1 phase instantaneous/definite-time overcurrent elements 67P1/67P1T.
67P1TC = 1
Setting 67P1TC set directly to logical 1:
Then only the corresponding directional control input from Figure 4.21 has
to be considered in the control of phase instantaneous/definite-time
overcurrent elements 67P1/67P1T.
If directional control enable setting E32 =N, then phase
instantaneous/definite-time overcurrent elements 67P1/67P1T are enabled
and nondirectional.
Note
: Some of the SEL
OGIC
Control Equation torque control settings are set
directly to logical 1 (e.g., 67P3TC = 1) for the factory default settings. See
SHO Command (Show/View Settings)
in
Section 10: Serial Port
Communications and Commands
for a list of the factory default settings.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......