Communications
Operation
Transmitting at longer intervals for baud rates above 9600 avoids overflowing
relays that receive M
IRRORED
B
ITS
at a slower rate.
Message Reception
Overview
During synchronized M
IRRORED
B
ITS
communications with the
communications channel in normal state, the relay decodes and checks each
received message. If the message is valid, the relay sends each received logic
bit (RMB
n
, where
n
= 1 through 8) to the corresponding pickup and dropout
security counters, that in turn set or clear the RMB
n
A and RMB
n
B relay
element bits.
Message Decoding
and Integrity Checks
Set the RX_ID of the local SEL-787 to match the TX_ID of the remote
SEL-787. The SEL-787 provides indication of the status of each M
IRRORED
B
ITS
communications channel with Relay Word bits ROKA (receive OK) and
ROKB. During normal operation, the relay sets the ROK
c
(
c
= A or B). Upon
detecting any of the following conditions, the relay clears the ROK
c
bit when:
➤
The relay is disabled.
➤
M
IRRORED
B
ITS
are not enabled.
➤
Parity, framing, or overrun errors.
➤
Receive message identification error.
➤
No message received in the time three messages have been sent
when PROTO = MB
c
, or seven messages have been sent when
PROTO = MB8
c
.
➤
Loopback is enabled.
The relay asserts ROK
c
only after successful synchronization as described
below and two consecutive messages pass all of the data checks described
above. After ROK
c
is reasserted, received data may be delayed while passing
through the security counters described below.
While ROK
c
is deasserted, the relay does not transfer new RMB data to the
pickup-dropout security counters described below. Instead, the relay sends one
of the user-definable default values to the security counter inputs. For each
RMB
n
, use the RXDFLT setting to determine the default state the M
IRRORED
B
ITS
should use in place of received data if an error condition is detected. The
setting is a mask of 1s, 0s, and/or Xs (for RMB1A–RMB8A), where X
represents the most recently received valid value. The positions of the 1s and
0s correspond to the respective positions of the M
IRRORED
B
ITS
in the Relay
).
is an extract of
, showing the positions of the M
IRRORED
B
ITS
.
Table I.1
Number of M
IRRORED
B
ITS
Messages for Different Baud
Baud Rate
Transmission Rate of M
IRRORED
B
ITS
Packets
2400
15 ms
4800
7.5 ms
9600
4 times a power system cycle (automatic pacing mode)
19200
4 times a power system cycle (automatic pacing mode)
38400
4 times a power system cycle (automatic pacing mode)
Содержание SEL-787
Страница 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 78: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 280: ...This page intentionally left blank ...
Страница 334: ...This page intentionally left blank ...
Страница 376: ...This page intentionally left blank ...
Страница 388: ...This page intentionally left blank ...
Страница 474: ...This page intentionally left blank ...
Страница 508: ...This page intentionally left blank ...
Страница 522: ...This page intentionally left blank ...