Date Code 20010719
701 Motor Protection Relay
Settings Calculation
Basic Motor Protection
4.21
specified points. For instance, the relay thermal limit characteristic
between 2.5 and 4.0 times Full Load Amps forms a continuous
curve between 225 seconds and 72 seconds.
Thermal Capacity Alarm Setting
Table 4.11
Thermal Capacity Alarm Setting
For all thermal element settings methods, the relay provides a thermal alarm.
When the motor thermal capacity used exceeds the Thermal Capacity Alarm Pickup
(TCAPU), the relay issues an alarm. The early alarm may allow you to correct the load
problem before a thermal trip occurs.
Thermal Capacity to Start Settings
Table 4.12
Thermal Capacity to Start Settings
The motor tripping and starting functions include supervision to help prevent a
thermal trip on a normal start. The relay prevents motor starting until the thermal
element has enough available thermal capacity to allow a motor start without tripping.
The available thermal capacity required to start is (100% – 10% – TCSTART), where
the Thermal Capacity Used To Start (TCSTART) setting or the relay can learn a value.
When you use the Use Learned Starting Thermal Capacity function
(TCLRNEN = Y), the relay records the thermal capacity used during the past five
starts and uses it in the thermal model in place of the Thermal Capacity Used to Start
setting. The relay adds 10% to the largest of the last five starting thermal capacities
and requires that the motor thermal model cool enough to permit that start.
EXAMPLE 4.7
Learned Starting Thermal Capacity Calculation
Over the past five starts, a motor has used 24%, 27%, 22%, 25%,
and 26% of thermal capacity. The largest thermal capacity to start
is 27%. The relay requires that the present thermal capacity drop
below 63% (100%–37%) before a new start is allowed.
Table 4.11
Thermal Capacity Alarm Setting
Setting Prompt
Setting Range
Setting Name =
Factory Default
Thermal Capacity Alarm Pickup
50%–100%
TCAPU = 90
Table 4.12
Thermal Capacity to Start Settings
Setting Prompt
Setting Range
Setting Name = Factory Default
Thermal Capacity
Used To Start
20%–100%
TCSTART = 85
Use Learned Starting
Thermal Capacity
Y, N
TCLRNEN = Y
Содержание SEL-701
Страница 12: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 20: ...This page intentionally left blank ...
Страница 36: ...This page intentionally left blank ...
Страница 64: ...This page intentionally left blank ...
Страница 144: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 232: ...This page intentionally left blank ...
Страница 246: ...This page intentionally left blank ...
Страница 346: ...This page intentionally left blank ...
Страница 390: ...This page intentionally left blank ...
Страница 408: ...This page intentionally left blank ...
Страница 410: ......
Страница 412: ......
Страница 414: ......
Страница 416: ......
Страница 418: ......
Страница 420: ......
Страница 422: ......
Страница 424: ......
Страница 426: ......
Страница 428: ......
Страница 430: ......
Страница 432: ......
Страница 434: ......
Страница 436: ......
Страница 438: ......
Страница 440: ......
Страница 442: ......
Страница 452: ...This page intentionally left blank ...
Страница 466: ...This page intentionally left blank ...