701 Motor Protection Relay
Date Code 20010719
Event Analysis
Example Event Report
9.16
Example Event Report
The example event report in
corresponds to the example Sequential
Events Recorder (SER) report in
. The boxed numbers in
match the SER row numbers in
. Row explanations follow
In
, the arrow (>) in the column following the IN or Vc column
identifies the “trigger” row, the row that corresponds to the Date and Time values at the
top of the event report.
The asterisk (*) in the column following the Vc column identifies the row where
the event summary data was taken. If the “trigger” row (>) and the summary row (*)
are the same, the * symbol takes precedence.
SEL-701 Date: 07/07/1999 Time: 14:39:47.907
MOTOR RELAY
FID=SEL-701-R100-V11Xxx-Z000000-D19990707 CID=1905
M L O/C RTD Out In
o o
t a444 555 WBOA
Currents (A Pri) Voltages (V Pri) o d679 000 drtm T2A 1357
IA IB IC IG IN VA VB VC r GN gghb 13 246
[1]
45.2 -180.6 145.2 9.8 -0.0 113 -265 151 R .A.. ... .... 1.. ....
256.0 -63.8 -125.4 66.8 -0.0 237 -21 -218 R .A.. ... .... 1.. ....
-45.2 180.2 -144.8 -9.8 0.1 -113 265 -151 R .A.. ... .... 1.. ....
-256.4 63.8 125.6 -67.0 0.0 -236 21 218 R .A.. ... .... 1.. ....
.
[2 cycles of event data removed]
.
[4]
46.4 -180.6 144.4 10.2 0.1 114 -265 150 R .A.. ... .... 1.. ....
255.6 -63.6 -124.6 67.4 0.0 236 -20 -219 R .A.. ... .... 1.. ....
-46.8 180.8 -144.2 -10.2 -0.1 -114 265 -150 R .A.. ... .... 1.. ....
-255.4 63.4 124.6 -67.4 -0.1 -236 20 219*R .T.. ... .... b.. ....
[5]
46.8 -180.8 144.0 10.0 0.1 114 -265 150 R .T.. ... .... b.. ....
255.8 -63.0 -124.8 68.0 0.1 236 -20 -219 R .T.. ... .... b.. ....
-47.0 180.6 -144.0 -10.4 -0.1 -114 265 -150 R .T.. ... .... b.. ....
-255.8 62.8 124.8 -68.2 0.0 -236 20 219 R .T.. ... .... b.. ....
.
[5 cycles of event data removed]
.
[10]
48.2 -180.8 144.0 11.4 0.0 116 -265 149 R .T.. ... .... b.. ....
255.4 -62.4 -125.0 68.0 0.0 236 -19 -220 R .T.. ... .... b.. ....
-48.0 180.8 -144.0 -11.2 0.0 -116 265 -149 R .T.. ... .... b.. ....
-192.4 29.2 111.8 -51.4 0.0 -236 19 220 R .... ... .... T.. ....
[11]
49.0 -127.4 89.6 11.2 0.0 116 -265 148 R .... ... .... T.. ....
64.8 2.0 -49.6 17.2 0.0 238 -19 -220 R .... ... .... T.. ....
-25.4 36.8 -17.4 -6.0 0.0 -117 265 -148 R .... ... .... T.. ....
0.0 0.0 0.0 0.0 0.0 -239 18 220 R .... ... .... T.. ....
[12]
0.0 0.0 0.0 0.0 -0.0 118 -265 148 . .... ... .... T.. ....
-0.2 0.0 0.0 -0.2 0.0 239 -18 -220 . .... ... .... T.. ....
.
[3.5 cycles of event data removed]
.
Continued on next page
Event Date & Time
Relay Firmware ID
Relay Firmware Checksum
One cycle of data
11
10
9
8
7
6
5
4
3
2
1
Содержание SEL-701
Страница 12: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 20: ...This page intentionally left blank ...
Страница 36: ...This page intentionally left blank ...
Страница 64: ...This page intentionally left blank ...
Страница 144: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 232: ...This page intentionally left blank ...
Страница 246: ...This page intentionally left blank ...
Страница 346: ...This page intentionally left blank ...
Страница 390: ...This page intentionally left blank ...
Страница 408: ...This page intentionally left blank ...
Страница 410: ......
Страница 412: ......
Страница 414: ......
Страница 416: ......
Страница 418: ......
Страница 420: ......
Страница 422: ......
Страница 424: ......
Страница 426: ......
Страница 428: ......
Страница 430: ......
Страница 432: ......
Страница 434: ......
Страница 436: ......
Страница 438: ......
Страница 440: ......
Страница 442: ......
Страница 452: ...This page intentionally left blank ...
Страница 466: ...This page intentionally left blank ...