2.15
Date Code 20170814
Instruction Manual
SEL-700G Relay
Installation
I/O Configuration
Step 16. Press the
ENT
pushbutton.
The front panel displays the following:
Accept New Config?
No Yes
Step 17. Select Yes and press the
ENT
pushbutton.
The front panel displays the following:
Config Accepted
Enter to Reboot
Step 18. Press the
ENT
pushbutton.
The relay restarts and the
ENABLED
light is turned on to indicate
the card was installed correctly.
After reconfiguration, the relay updates the part number, except
for the following indicated digits. These digits remain
unchanged, i.e., these digits retain the same character as before
the reconfiguration. Also, a communications card installed in
Slot
C
will be reflected as an empty slot in the part number. A
regular 4 DI/4 DO card and a hybrid 4 DI/4 DO card have the
same device ID. When interchanging these two cards, the part
number for the respective slots should be updated manually.
Use the Status command to view the part number.
Use the PARTNO command from the 2AC level to enter the
exact part number of the relay.
Step 19. Update the side-panel drawing with the drawing sticker
provided in the card kit. If necessary, replace the rear panel
with the one applicable for the card and attach the terminal-
marking label provided with the card to the rear-panel cover.
Step 20. Reconnect all connection plugs and add any additional wiring/
connectors required by the new card.
Slot B CPU Board Replacement
When replacing the Slot B card, please be aware of the following
considerations.
➤
The new card will have the latest firmware when shipped from
the factory.
➤
Table A.1 in Appendix A: Firmware and Manual Versions
should be reviewed for firmware changes and new or revised
settings to check if any existing settings in the relay, or the
application of the relay, will be affected.
➤
If the IEC 61850 protocol option was used previously, verify
that the IEC 61850 protocol is still operational after the
replacement. If the protocol is not operational, re-enable the
protocol. Refer to Relays With IEC 61850 Option for the
verification process.
➤
Save all the settings and event reports before replacing the card.
PART NUM = 0700G11ACA1D7281020X
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...