6.6
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
230 kV Overhead Distribution Line Example
Use Level 1 high-set instantaneous phase overcurrent element for SOTF protec-
tion.
E50P :=
1
.
Phase Instantaneous/Definite-Time Overcurrent Elements (N, 1–4)
This application does not require residual ground overcurrent protection.
E50G :=
N
.
Residual Ground Instantaneous/Definite-Time Overcurrent Ele-
ments (N, 1–4)
This application does not require negative-sequence overcurrent protection.
E50Q :=
N
.
Negative-Sequence Instantaneous/Definite-Time Overcurrent Ele-
ments (N, 1–4)
Use inverse-time overcurrent protection to provide backup protection for high-
resistance ground faults. The 51S1 element provides backup protection for unbal-
anced faults if the step distance protection fails to operate.
E51S :=
1
.
Selectable Inverse-Time Overcurrent Element (N, 1–3)
Set E32 to AUTO or AUTO2 and the relay automatically calculates the settings
corresponding to the ground directional element (32G).
E32 :=
AUTO2
.
Directional Control (Y, AUTO, AUTO2)
Communications-assisted tripping is not required.
ECOMM :=
N
.
Communications-Assisted Tripping (N, DCB, POTT, POTT2,
POTT3, DCUB1, DCUB2)
Fuses or molded case circuit breakers often protect potential transformers. Oper-
ation of one or more fuses, or molded case circuit breakers, results in a loss of
polarizing potential inputs to the relay. Loss of one or more phase voltages pre-
vents the relay from properly determining fault distance or direction.
Occasional loss-of-potential (LOP) to the distance relay, while unavoidable, is
detectable. When the relay detects the loss-of-potential, the relay can block dis-
tance element operation, block or enable forward directional overcurrent ele-
ments, and issue an alarm for any true LOP condition.
NOTE:
If line-side PTs are used, the
circuit breaker(s) must be closed for
the LOP logic to detect an LOP
condition. Therefore, if three-phase
potential to the relay is lost while the
circuit breaker(s) is open (e.g., the PT
fuses are removed while the line is de-
energized), the relay cannot detect an
LOP when the circuit breaker(s) closes
again.
Set ELOP to Y1 for this application example. This choice reduces the chances of
false tripping because of a loss-of-potential condition.
ELOP :=
Y1
.
Loss-of-Potential (Y, Y1, N)
You do not need Advanced Settings for this application example.
EADVS :=
N
.
Advanced Settings (Y, N)
Table 6.3
LOP Enable Options
Option
Description
N
The LOP logic operates but does not disable voltage-polarized directional ele-
ments, distance elements, and forward directional overcurrent elements. Use
LOP in this case for alarm only.
Y
The relay disables all voltage-polarized directional elements and distance ele-
ments, but enables forward directional overcurrent elements. These forward
directional overcurrent elements effectively become nondirectional and provide
overcurrent protection during an LOP condition.
Y1
The relay disables all voltage-polarized directional elements and distance ele-
ments. The relay also disables the overcurrent elements controlled by the volt-
age-polarized directional elements.
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...