Date Code 20020129
Differential, Restricted Earth Fault,
3-21
Overcurrent, Voltage, and Frequency Elements
SEL-387E Instruction Manual
choose W3CTC = 5 as the setting. The process is almost complete, except for a final
check.
5. Ensure that there will be no wye windings with wye CTs and a setting of WnCTC = 0. In
this case the primary winding is wye-connected and has wye-connected CTs. In step 4
we set W1CTC at zero because Winding 1 was the reference winding. However, this
setting violates the condition that WnCTC not equal 0. Instead of a zero shift, we must
shift Winding 1 360 degrees by setting W1CTC = 12. This solves the zero-sequence
current problem. The process is now complete. The relay receives the three settings as
W1CTC = 12, W2CTC = 7, and W3CTC = 5.
Winding Line-to-Line Voltages
Enter the nominal line-to-line transformer terminal voltages. If a load tap changer is included in
the transformer differential zone, assume that it is in the neutral position. The setting units are
kilovolts.
Current TAP
The relay uses a standard equation to set TAPn, based on settings entered for the particular
winding. (n denotes the winding number.)
C
•
CTRn
VWDGn
•
3
1000
MVA
TAPn
¼
¼
=
where:
C
=
1 if WnCT setting = Y (wye-connected CTs)
C
=
if WnCT setting = D (delta-connected CTs)
MVA
=
maximum power transformer capacity setting
(must be the same for all TAPn calculations)
VWDGn =
winding line-to-line voltage setting, in kV
CTRn
=
current transformer ratio setting
The relay calculates TAPn with the following limitations:
The tap settings are within the range 0.1 • I
N
and 31 • I
N
The ratio TAP
MAX
/TAP
MIN
7.5
Restrained Element Operating Current Pickup
The O87P setting range is 0.1 to 1.0; we suggest an O87P setting of 0.3. The setting must be at a
minimum for increased sensitivity but high enough to avoid operation because of steady-state CT
error and transformer excitation current. The setting must also yield an operating current greater
than or equal to 0.1 • I
N
, when multiplied by the smallest of TAP1 through TAP3. Stated another
way,
O87P
MIN
(0.1 • I
N
) / TAP
MIN
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......