9-14
Event Reports and Sequential Events Reporting
Date Code 20010521
SEL-387E Instruction Manual
n
Event number; defaults to 1 if not listed, where 1 is the most recent event.
Sx
Display x samples per cycle (4 or 8); defaults to 4 if not listed.
Ly
Display y cycles of data (1 to LER); defaults to LER if not listed.
Ly-
Display from cycle y to end of report.
Ly-w
Display from cycle y to cycle w.
Refer to Figure 9.4 for an example differential event report. This example event report displays
rows of information each quarter-cycle; it was retrieved with the
EVE DIF1<ENTER>
command.
=>>EVE DIF1<ENTER>
XFMR 1 Date: MM/DD/YY Time: HH:MM:SS.SSS
STATION A
FID=SEL-387E-R-V-Z-D
Differential Set 1 Set 2 Set 3
Differential Quantities 87 87B HB TR TRP LT LT OUT IN
Multiples of TAP R HE 13 VVVV13 VVVV13 VVVVVVVV 1357 135
IOP1 IRT1 I1F2 I1F5 U123 123 123 5F 24 123424 123424 12345678 246A 246
[1]
123.12 123.12 123.12 123.12 .... ... ... .. .. ...... ...... ........ .... ...
123.12 123.12 123.12 123.12 .... ... ... .. .. ...... ...... ........ .... ...
123.12 123.12 123.12 123.12 .... ... ... .. .. ...... ...... ........ .... ...
123.12 123.12 123.12 123.12 .... ... ... .. .. ...... ...... ........ .... ...
[2]
123.12 123.12 123.12 123.12>.... ... ... .. .. ...... ...... ........ .... ...
123.12 123.12 123.12 123.12 .... ... ... .. .. ...... ...... ........ .... ...
123.12 123.12 123.12 123.12 .... ... ... .. .. ...... ...... ........ .... ...
123.12 123.12 123.12 123.12*.... ... ... .. .. ...... ...... ........ .... ...
.
.
.
[15]
123.12 123.12 123.12 123.12 .... ... ... .. .. ...... ...... ........ .... ...
123.12 123.12 123.12 123.12 .... ... ... .. .. ...... ...... ........ .... ...
123.12 123.12 123.12 123.12 .... ... ... .. .. ...... ...... ........ .... ...
123.12 123.12 123.12 123.12 .... ... ... .. .. ...... ...... ........ .... ...
Event: TRIP1 TRIP2 TRIP3 TRIP4
Targets: TRIP INST 87-1 87-2 87-3 24 81 A B C N W1 W2 W3 50/51
Winding 1 Currents (A Sec), ABC: 123.1 123.1 123.1
Winding 2 Currents (A Sec), ABC: 123.1 123.1 123.1
Winding 3 Currents (A Sec), ABC: 123.1 123.1 123.1
Winding X Voltages (V Sec), ABC: 123.1 123.1 123.1
Volts/Hertz Percent: 123.1
=>>
Figure 9.4: Example Differential Event Report
The trigger row includes a ‘>’ character following immediately after the last analog column to
indicate the trigger point. A ‘*’ character following immediately after the last analog column
denotes that the designated row was used for the Event Summary currents. The ‘*’ character
takes precedence over the ‘>’ character when both conditions occur for the same row.
The following table summarizes the event report current columns.
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......