Date Code 20020129
Front-Panel Interface
8-3
SEL-387E Instruction Manual
underscored. Use the up/down arrow keys to scroll and set the first character of the password.
Passwords are case sensitive; be sure you use upper- or lower-case letters as needed. Use the
right arrow key to move to the second character, and adjust it using the up/down arrows as
before. Continue this process until
all six
characters are filled. If the password has fewer than
six characters, fill the remaining slots with a “blank,” found between the numeral 9 and the
lower-case “a” in the character scroll. When the password is complete, push
<SELECT>
to
enter it. If the password is correct, the relay will change to the higher level and permit you to
perform the commands of that level. If it is incorrect, the relay will declare an “Invalid
Password” and allow another attempt. After three incorrect attempts, the relay will pulse the
ALARM contact for one second and the front panel will exit the command you are trying to
access.
P
USHBUTTONS
Eight multifunction pushbuttons control the front-panel display. The button legend defines the
primary function in the top row and the secondary function in the bottom row. The primary
functions are for command selection, while the secondary functions are for cursor movements
and specific commands within dialogues. The eight pushbutton primary functions will be
discussed in the order in which they appear from left to right on the front panel.
Primary Function Review
TARGET RESET/LAMP TEST
The left-most button is dedicated to the
<TARGET RESET>
function. Except while viewing or
editing settings, pressing
<TARGET RESET>
causes the front-panel LEDs to illuminate for a
two-second lamp test and then clear all target LEDs except for the EN LED, which is illuminated
if the relay is enabled. While viewing or editing settings, the
<TARGET RESET>
button acts
as a Help function, showing specific information about the displayed setting.
METER
The
<METER>
button performs all of the
MET
serial port commands, via a multilevel menu
structure. The METER display is updated every two seconds.
While within the METER menu structure, the
<CANCEL>
button will take the user back up to
the previous menu. The
<EXIT>
button will take the user out of METER and back to the default
display.
While METER information is being scrolled every two seconds, the scroll can be stopped by
pushing
<SELECT>
. The user may then manually scroll through the displays with the up/down
arrow keys. This facilitates writing down the displayed information by hand, for example.
Pushing
<SELECT>
again will resume the scroll.
Figure 8.5, at the end of this section, shows the full METER menu and display structure.
When
<METER>
is pushed, the seven dual-function buttons revert to their secondary functions.
The first METER menu prompts the user to select the
W1
,
W2
,
W3
,
V
,
CMBO
,
DIF
,
DC
,
F
,
PWR
, or
ENG
metering display. W1 to W3 are winding displays, V is the voltage input display,
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......