Date Code 20020129
Serial Port Communications and Commands
7-29
SEL-387E Instruction Manual
Setting
specifies the setting name with which to begin. The default is the first setting.
TERSE
eliminates the display of the port settings at the end of the setting procedure.
The command will function properly if just
TE
is entered, instead of the full word.
The SET P procedure works just like the SET procedure. Table 7.4 lists the editing keys that you
can use with the
SET
command.
The settings for each communication port are:
PROTO
: protocol can be SEL, LMD, or DNP.
PREFIX
: If PROTO is LMD, prefix can be @, #, $, %, or &.
ADDR
:
If PROTO is LMD, ADDR can be any integer 1 through 99.
SETTLE
: If PROTO is LMD, the settling time can be 0 to 30 seconds.
SPEED
:
baud can be set to 300, 1200, 2400, 4800, 9600, or 19200.
BITS
:
data can be 7 or 8 bits.
PARITY
: can be O, E, or N (Odd, Even, None).
STOP
:
bits can be 1 or 2.
T_OUT
:
port inactivity time-out can be 0 through 30 minutes. T_OUT = 0 setting means
port will never time-out. Time-out returns port to Access Level 0.
AUTO
:
send auto messages to the port; Yes or No.
RTSCTS
: enable hardware handshaking; Yes or No (only if PROTO=SEL).
FASTOP
: enable
Fast Operate
function; Yes or No.
Refer to individual elements in
Section 3: Differential, Restricted Earth Fault, Overcurrent,
Voltage, and Frequency Elements
and to
Section 6: Setting the Relay
for information on
settings.
SET R (Edit SER Settings)
Access Level 2
Configure the Sequential Events Recorder settings using the
SET R
command. The settings are
the four sequential events record trigger conditions (SER1 to SER4) and the ALIAS1 to
ALIAS20 settings for renaming Relay Word bits for the SER report. The entire syntax of the
SET R
command follows:
SET R
Setting
TERSE<ENTER>
The two parameters are optional and perform the following functions:
Setting
specifies the setting name with which to begin. The default is the first setting.
TERSE
eliminates the display of the new settings at the end of the setting procedure.
The command will function properly if just
TE
is entered, instead of the full word.
The SET R procedure works just like the SET procedure. Table 7.4 lists the editing keys that
you can use with the
SET
command.
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......