4-16
Control Logic
Date Code 20020129
SEL-387E Instruction Manual
LED 10 – B – B-Phase Involved in the Fault (Programmable LEDB)
LED 10 is programmable via the LEDB SEL
OGIC
control equation Global setting. It is updated
each processing interval. If LEDB is true, LED 10 is illuminated. Otherwise, it is reset. The
factory default setting is LEDB = OCB + 87E2.
Relay Word bit OCB indicates B-phase overcurrent during the fault. It is derived by first
checking which winding “Wn” LED is lit, then asserting if the associated 50Bn4 overcurrent
element bit is asserted, or if the magnitude of the IBWn phase current is greater than or equal to
the magnitudes of IAWn and ICWn.
Relay Word bit 87E2 indicates differential element 87-2 operation and follows LED 5 operation
(see LED 5 discussion).
LED 11 – C – C-Phase Involved in the Fault (Programmable LEDC)
LED 11 is programmable via the LEDC SEL
OGIC
control equations Global setting. It is updated
each processing interval. If LEDC is true, LED 11 is illuminated. Otherwise, it is reset. The
factory default setting is LEDC = OCC + 87E3.
Relay Word bit OCC indicates C-phase overcurrent during the fault. It is derived by first
checking which winding “Wn” LED is lit, then asserting if the associated 50Cn4 overcurrent
element bit is asserted or if the magnitude of the ICWn phase current is greater than or equal to
the magnitudes of IAWn and IBWn.
Relay Word bit 87E3 indicates differential element 87-3 operation and follows LED 6 operation
(see LED 6 discussion).
LED 12 – N – Residual Overcurrent Element Trip
This LED will illuminate if any residual overcurrent element present in the TR1 through TR4
settings is asserted at the rising edge of the trip or one cycle later. Applicable elements include
any of the winding overcurrent elements indicated by Relay Word bits “50N**,” “50N**T,” or
“51N*T.” The combined overcurrent element indicated by Relay Word bit 51NC1T is also
included. LED 12 remains lit until reset by the TRGTR element. TRGTR is asserted for one
cycle either via the TARGET RESET pushbutton on the front panel or via the serial port
command
TAR R
.
LED 13 – W1 – Winding 1 Overcurrent Element Operation
This LED will illuminate if any Winding 1 overcurrent element present in the TR1 through TR4
settings is asserted at the rising edge of the trip or one cycle later. Applicable elements include
any of the 23 Relay Word bits associated with Winding 1 overcurrent elements. LED 13 remains
lit until reset by the TRGTR element. TRGTR is asserted for one cycle either via the TARGET
RESET pushbutton on the front panel or via the serial port command
TAR R
.
LED 14 – W2 – Winding 2 Overcurrent Element Operation
This LED will illuminate if any Winding 2 overcurrent element present in the TR1 through TR4
settings is asserted at the rising edge of the trip or one cycle later. Applicable elements include
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......