Date Code 20020129
Control Logic
4-15
SEL-387E Instruction Manual
LED 5 – 87-2 – Differential Element 2
This LED will illuminate if the differential elements 87R or 87U are present in the TR1 through
TR4 settings, and Relay Word bits 87R2 and 87R, or 87U2, are found to be asserted at the rising
edge of any trip or one cycle later. If so, the 87E2 bit is also set. LED 5 remains lit until reset by
the TRGTR element. TRGTR is asserted for one cycle either via the TARGET RESET
pushbutton on the front panel or via the serial port command
TAR R
.
LED 6 – 87-3 – Differential Element 3
This LED will illuminate if the differential elements 87R or 87U are present in the TR1 through
TR4 settings, and Relay Word bits 87R3 and 87R, or 87U3, are found to be asserted at the rising
edge of any trip or one cycle later. If so, the 87E3 bit is also set. LED 6 remains lit until reset by
the TRGTR element. TRGTR is asserted for one cycle either via the TARGET RESET
pushbutton on the front panel or via the serial port command
TAR R
.
LED 7 – 81 – Over-/Underfrequency Element Trip
This LED will illuminate if any over-/underfrequency element present in the TR1 through TR4
settings is asserted at the rising edge of any trip or one cycle later. Over-/underfrequency
elements include
81Dn and 81DnT
(1< n <6)
.
LED 8 remains lit until reset by the TRGTR
element. TRGTR is asserted for one cycle either via the TARGET RESET pushbutton on the
front panel or via the serial port command
TAR R
.
LED 8 – 24 – Volts-per-Hertz Element
This LED will illuminate if any volts/hertz element present in the TR1 through TR4 settings is
asserted at the rising edge of any trip or one cycle later. Volts/hertz elements include
24D1,
24D1T, 24C2, and 24C2T.
LED 7 remains lit until reset by the TRGTR element. TRGTR is
asserted for one cycle either via the TARGET RESET pushbutton on the front panel or via the
serial port command
TAR R
.
LED 9 – A – A-Phase Involved in the Fault (Programmable LEDA)
LED 9 is programmable via the LEDA SEL
OGIC
control equations Global setting. It is updated
each processing interval. If LEDA is true, LED 9 is illuminated. Otherwise, it is reset. The
factory default setting is LEDA = OCA + 87E1.
Relay Word bit OCA indicates A-phase overcurrent during the fault. It is derived by first
checking which winding “Wn” LED is lit, then asserting if the associated 50An4 overcurrent
element bit is asserted, or if the magnitude of the IAWn phase current is greater than or equal to
the magnitudes of IBWn and ICWn.
Relay Word bit 87E1 indicates differential element 87-1 operation, and follows LED 4 operation
(see LED 4 discussion).
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......