4-12
Control Logic
Date Code 20020129
SEL-387E Instruction Manual
Operation of Output Contacts for Different Output Contact Types
Output Contacts OUT101 through OUT107
The execution of the serial port command
PULSE xxx
(xxx = OUT101–OUT107, OUT201–
OUT212), asserts the corresponding Relay Word bit (e.g., OUT104) to logical 1, for one or more
seconds as defined by the user. The assertion of SEL
OGIC
control equation setting OUTm (m =
101–107, 201–212) to logical 1 also asserts the corresponding Relay Word bit OUTm to
logical 1.
The assertion of Relay Word bit OUTm to logical 1 causes the energization of the corresponding
output contact OUTm coil. Depending on the contact type (a or b), the output contact closes or
opens. An “a” type output contact is open when the output contact coil is de-energized and
closed when the output contact coil is energized. A “b” type output contact is closed when the
output contact coil is de-energized and open when the output contact coil is energized. Solder
jumpers JMP22 through JMP29 (main board) and JMP17 through JMP28 (interface board)
permit the user to configure any OUTm contact to either an “a” or “b” type. OUT101 through
OUT107 are factory configured as type “a,” as are OUT201 through OUT212 if the additional
interface board is ordered.
The state of OUTm remains the same while a setting change is in progress. However, once the
new settings are enabled, the SEL
OGIC
control equation setting for OUTm will determine the
new state of OUTm.
OUT107 coil operation may be set to follow that of the ALARM contact by setting jumper
JMP23 in the left position on the main board. OUT107 then will not respond to Relay Word bit
OUT107. The OUT107 contact configuration can be set as “a” or “b,” as noted above. See
Section 2: Installation
, for more information.
ALARM Output Contact
When the relay is functioning properly, the alarm logic/circuitry keeps the ALARM output
contact coil energized. The type “b” ALARM output contact is normally held open. Solder
jumper JMP21 may also be configured by the user for a type “a” contact, if desired.
To verify ALARM output contact functionality, execute the serial port command
PULSE
ALARM
. Execution of this command momentarily de-energizes the ALARM output contact
coil.
The Relay Word bit NOTALM (not ALARM) is asserted to logical 1, and the ALARM output
contact coil is energized, when the SEL-387E Relay is operating correctly. When the serial port
command
PULSE ALARM
(or front-panel CNTRL ALARM) is executed, the NOTALM Relay
Word bit momentarily deasserts to logical 0. Also, when the relay enters Access Level 2 or
Access Level B, or a settings change is made, the NOTALM Relay Word bit momentarily
deasserts to logical 0. When NOTALM is zero, the ALARM output contact coil is de-energized
momentarily and the “b” contact closes. The ALARM contact also closes when a loss of power
occurs.
Содержание SEL-387E
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 50: ......
Страница 124: ......
Страница 176: ......
Страница 196: ......
Страница 198: ......
Страница 242: ......
Страница 270: ......
Страница 308: ......
Страница 422: ......
Страница 428: ......
Страница 432: ......
Страница 448: ......
Страница 450: ......
Страница 462: ......