G-4
Setting SEL
OGIC
®
Control Equations
Date Code 20020215
SEL-351R Instruction Manual
SEL
OGIC
Control Equation Parentheses Operator ( )
More than one set of parentheses ( ) can be used in a SEL
OGIC
control equation setting. For
example, the following SEL
OGIC
control equation setting has two sets of parentheses:
SV7 = (SV7+IN101)*(50P1+50N1)
In the above example, the logic within the parentheses is processed first and then the two
parentheses resultants are ANDed together. The above example is from Figure 7.25 in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
. Parentheses cannot be “nested”
(parentheses within parentheses) in a SEL
OGIC
control equation setting.
SEL
OGIC
Control Equation NOT Operator !
The NOT operator ! is applied to a single Relay Word bit and also to multiple elements (within
parentheses). Following are examples of both.
Example of NOT Operator ! Applied to Single Element
The internal circuit breaker status logic in the
SEL-
351R operates on 52a circuit breaker auxiliary
contact logic. The SEL
OGIC
control equation circuit breaker status setting is labeled 52A. See
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
and
Close
Logic
in
Section 6: Close and Reclose Logic
for more information on SEL
OGIC
control
equation circuit breaker status setting 52A.
When a circuit breaker is closed, the 52a circuit breaker auxiliary contact is closed. When a
circuit breaker is open, the 52a contact is open.
The opposite is true for a 52b circuit breaker auxiliary contact. When a circuit breaker is closed,
the 52b circuit breaker auxiliary contact is open. When the circuit breaker is open, the 52b
contact is closed.
If a 52a contact is connected to optoisolated input IN101, the SEL
OGIC
control equation circuit
breaker status setting 52A is set:
52A = IN101
Conversely, if a 52b contact is connected to optoisolated input IN1, the SEL
OGIC
control
equation circuit breaker status setting 52A is set:
52A = !IN101
[=NOT(IN101)]
With a 52b contact connected, if the circuit breaker is closed, the 52b contact is open and input
IN1 is deenergized [IN1 = 0 (logical 0)]:
52A = !IN101 = NOT(IN101) = NOT(0) = 1
Thus, the SEL
OGIC
control equation circuit breaker status setting 52A sees a closed circuit
breaker.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......