SET EZ and SET FZ Commands (Change EZ Settings)
The
SET EZ
n
command allows you to change the EZ recloser control settings for settings
group n (n specifies the settings group—1, 2, 3, 4, 5, or 6). These settings are the traditional
recloser control setting (e.g., min. trip, fast curve, delay curve, operations to lockout settings)
and other special recloser control scheme logic (e.g., cold load pickup, sequence coordination
logic).
The EZ recloser control settings for a given setting group n override and change a number of the
“regular” settings in the same setting group n (set with the SET n command, in Access Level 2)
if the group number n is encompassed by the global setting EZGRPS (set with the SET G
command, in Access Level 2)—see Table 1.1. Global setting EZGRPS enables the EZ settings
in the encompassed settings groups.
For example, if EZGRPS = 2 (the factory setting), then you can make EZ recloser control
settings for settings groups 1 (main settings) and 2 (alternate settings) with the SET EZ 1 and
SET EZ 2 commands, respectively. The EZ recloser control settings for settings groups 1 and 2
also override a number of the “regular” settings in the respective setting group. If EZGRPS = 2,
the EZ settings for settings groups 3 through 6 cannot be made, nor are the EZ settings for
settings groups 3 through 6 active (none of the “regular” settings in settings groups 3 through 6
are overridden).
The
SET FZ
command allows you to change the EZ global settings. The EZ global settings also
override a number of the “regular” global settings (set with the SET G command, in Access
Level 2) if global setting EZGRPS > 0—see end of Table 1.1.
Access Level B Commands
Access Level B commands primarily allow you to operate control parameters and output
contacts without allowing you access to change settings. All Access Level 1 and Access Level E
commands can also be executed from Access Level B. The screen prompt is: ==>
BRE n Command (Preload/Reset Breaker Wear)
Use the
BRE W
command to preload breaker/recloser contact wear. For example, to preload the
breaker/recloser wear to 25 percent, 28 percent, and 24 percent for the respective phases, issue
the following command.
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......