Date Code 20020215
Setting the SEL-351R Recloser Control
9-1
SEL-351R Instruction Manual
SECTION 9: SETTING THE SEL-351R RECLOSER CONTROL
I
NTRODUCTION
Change or view settings with the SET and SHOWSET serial port commands and the front-panel
SET pushbutton. Table 9.1 lists the serial port SET commands.
Table 9.1: Serial Port SET Commands
Command
Settings
Type
Description
Settings
Sheets
SET n
Group
“Regular” settings (e.g., overcurrent elements,
voltage elements, reclose timers) for settings group n
(n = 1, 2, 3, 4, 5, 6).
1–12*
SET L n
Logic
SEL
OGIC
®
control equations for settings group n
(n = 1, 2, 3, 4, 5, 6).
13–19*
SET G
Global
Breaker monitor, battery monitor, optoisolated input
debounce timers, etc.
20–22*
SET R
SER
Sequential Events Recorder trigger conditions and
Load Profile settings.
23*
SET T
Text
Front-panel default display and local control text.
24–27*
SET P n
Port
Serial port settings for serial port n (n = 1, 2, 3, or F).
28*
SET EZ n
EZ Recloser
Control
Traditional recloser control settings (e.g., minimum
trips, fast/delay curves, reclose intervals) for settings
group n (n = 1, 2, 3, 4, 5, 6)
1–3**
SET FZ
EZ Global
Automatic recloser monitor, battery monitor, etc.
3**
* located at the end of this section
** located at the end of the
Settings
section in the
SEL-351R Quick-Start Installation and User’s Guide
.
View settings with the respective serial port SHOWSET commands (SHO, SHO L, SHO G,
SHO R, SHO T, SHO P, SHO EZ, SHO FZ). See
SHO Command (Showset)
in
Section 10:
Serial Port Communications and Commands
.
Refer to the
Settings
section in the
SEL-351R Quick-Start Installation and User’s Guide
for
information on setting traditional recloser control settings with the SET EZ n and SET FZ
commands. See
SET EZ and SET FZ Commands (Change EZ Settings
) in the
Access Level E
(EZ) Commands
subsection of
Section 10: Serial Port Communications and Commands
for
information on EZ recloser control and EZ global settings (SET EZ n and SET FZ, respectively),
and on overriding certain “regular” group settings and global settings (SET n and SET G,
respectively).
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...