7-34
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20020215
SEL-351R Instruction Manual
Settings Example
Three output contacts can be used for the following functions:
OUT101 = TRIP
(overcurrent tripping/manual tripping; see
Section 5: Trip and
Target Logic
)
OUT102 = CLOSE
(automatic reclosing/manual closing; see
Section 6: Close and
Reclose Logic
)
OUT103 = SV1T
(breaker failure trip; see
SEL
OGIC
Control Equation
Variables/Timers
earlier in this section)
OUT104 = 0
(output contact OUT104 not used—set equal to zero)
.
.
.
OUT107 = 0
(output contact OUT107 not used—set equal to zero)
Operation of Output Contacts for Different Output Contact Types
Output Contacts OUT101 Through OUT107
The execution of the serial port command PULSE n (n = OUT101 through OUT107) asserts the
corresponding Relay Word bit (OUT101 through OUT107) to logical 1. The assertion of
SEL
OGIC
control equation setting OUTm (m = 101 through 107) to logical 1 also asserts the
corresponding Relay Word bit OUTm (m = 101 through 107) to logical 1.
The assertion of Relay Word bit OUTm (m = 101 through 107) to logical 1 causes the
energization of the corresponding output contact OUTm coil. Depending on the contact type (a
or b), the output contact closes or opens as demonstrated in Figure 7.27. An “a” type output
contact is open when the output contact coil is deenergized and closed when the output contact
coil is energized. A “b” type output contact is closed when the output contact coil is deenergized
and open when the output contact coil is energized.
Notice in Figure 7.27 that all four possible combinations of output contact coil states (energized
or deenergized) and output contact types (a or b) are demonstrated. See
Output Contact
Jumpers
in
Section 2: Additional Installation Details
for output contact type options.
Output contact pickup/dropout time is 4 ms.
ALARM Output Contact
Refer to Figure 7.27 and
Relay Self-Tests
in
Section 13: Testing and Troubleshooting
.
When the relay is operational, the ALARM output contact coil is energized. The alarm
logic/circuitry keeps the ALARM output contact coil energized. Depending on the ALARM
output contact type (a or b), the ALARM output contact closes or opens as demonstrated in
Figure 7.27. An “a” type output contact is open when the output contact coil is deenergized and
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......