Date Code 20020215
Inputs, Outputs, Timers, and Other Control Logic
7-29
SEL-351R Instruction Manual
If the individual settings change causes a change in one or more SEL
OGIC
control equation
settings SS1 through SS6, the active setting group can be changed, subject to the newly enabled
SS1 through SS6 settings.
Note: Make Active Setting Group Switching Settings With Care
The active setting group is stored in nonvolatile memory so it can be retained during power loss
or settings change. The nonvolatile memory is rated for a finite number of “writes” for all
setting group changes. Exceeding this limit can result in an EEPROM self-test failure. This
limit translates to an average of 1 setting group change per day for a 25-year relay service life.
Therefore, set equations SS1 through SS6 with care so continuous cyclical changing of the active
setting group does not occur. Time setting TGR qualifies settings SS1 through SS6 before
changing the active setting group. If optoisolated inputs IN101 through IN106 are used in
settings SS1 through SS6, the inputs have their own built-in debounce timer that can help in
providing the necessary time qualification (see Figure 7.1).
SEL
OGIC
C
ONTROL
E
QUATION
V
ARIABLES
/T
IMERS
Sixteen (16) SEL
OGIC
control equation variables/timers are available. Each SEL
OGIC
control
equation variable/timer has a SEL
OGIC
control equation setting input and variable/timer outputs
as shown in Figure 7.23 and Figure 7.24.
Timers SV1T through SV6T in Figure 7.23 have a setting range of a little over 4.5 hours:
0.00–999999.00 cycles in 0.25-cycle increments
Timers SV7T through SV16T in Figure 7.24 have a setting range of almost 4.5 minutes:
0.00–16000.00 cycles in 0.25-cycle increments
These timer setting ranges apply to both pickup and dropout times (SVnPU and SVnDO,
n = 1 through 16).
Содержание SEL-351R
Страница 12: ......
Страница 14: ......
Страница 18: ......
Страница 74: ......
Страница 76: ......
Страница 82: ......
Страница 136: ......
Страница 140: ......
Страница 176: ......
Страница 180: ......
Страница 196: ...5 16 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 6 POTT Logic ...
Страница 202: ...5 22 Trip and Target Logic Date Code 20020215 SEL 351R Instruction Manual Figure 5 10 DCUB Logic ...
Страница 332: ......
Страница 334: ......
Страница 460: ......
Страница 466: ......
Страница 476: ......
Страница 478: ......
Страница 510: ......
Страница 512: ......
Страница 522: ......
Страница 548: ......
Страница 550: ......
Страница 576: ......
Страница 610: ......
Страница 616: ......