3-20
Overcurrent, Voltage, Synchronism Check, Frequency, and Power Elements
Date Code 20001006
SEL-351 Instruction Manual
Control of Logic Point TCP
Refer to Figure 3.14.
The Torque Control Switch is controlled by logic point TCP. Logic point TCP is controlled by
directional control (optional) and SEL
OGIC
Control Equation torque control setting 51PTC.
If logic point TCP = logical 1, the Torque Control Switch is closed and maximum phase current,
I
P
, is routed to the pickup comparator (setting 51PP) and the curve timing/reset timing functions.
If logic point TCP = logical 0, the Torque Control Switch is open and maximum phase current, I
P
,
cannot get through to the pickup comparator and the curve timing/reset timing functions. The
maximum phase current, I
P
, effectively appears as a magnitude of zero (0) to the pickup com-
parator and the curve timing/reset timing function.
Directional Control Option
Refer to Figure 3.14.
See Figure 4.18 in
Section 4: Loss-of-Potential, Load Encroachment, and Directional Element
Logic
for more information on the optional directional control. If the directional control enable
setting E32 is set:
E32 = N
then directional control is defeated, and the directional control input into logic point TCP in
Figure 3.14 is asserted to logical 1 continuously. Then, only the corresponding SEL
OGIC
Control
Equation torque control setting 51PTC has to be considered in the control of logic point TCP (and ,
thus, in the control of the Torque Control Switch and phase time-overcurrent element 51PT).
Torque Control
Refer to Figure 3.14.
SEL
OGIC
Control Equation torque control settings (e.g., 51PTC) cannot be set directly to logical 0.
The following are setting examples of SEL
OGIC
Control Equation torque control setting 51PTC for
phase time-overcurrent element 51PT.
51PTC = 1
Setting 51PTC set directly to logical 1:
Then only the corresponding directional control input from Figure 4.18 has
to be considered in the control of logic point TCP (and, thus, in the control
of the Torque Control Switch and phase time-overcurrent element 51PT).
If directional control enable setting E32 = N, then logic point
TCP = logical 1 and, thus, the Torque Control Switch closes and phase
time-overcurrent element 51PT is enabled and nondirectional.
Содержание SEL-351
Страница 14: ...Courtesy of NationalSwitchgear com ...
Страница 16: ...Courtesy of NationalSwitchgear com ...
Страница 40: ...Courtesy of NationalSwitchgear com ...
Страница 74: ...Courtesy of NationalSwitchgear com ...
Страница 146: ...Courtesy of NationalSwitchgear com ...
Страница 186: ...Courtesy of NationalSwitchgear com ...
Страница 220: ...Courtesy of NationalSwitchgear com ...
Страница 304: ...Courtesy of NationalSwitchgear com ...
Страница 340: ...Courtesy of NationalSwitchgear com ...
Страница 380: ...Courtesy of NationalSwitchgear com ...
Страница 450: ...Courtesy of NationalSwitchgear com ...
Страница 506: ...Courtesy of NationalSwitchgear com ...
Страница 528: ...Courtesy of NationalSwitchgear com ...
Страница 534: ...Courtesy of NationalSwitchgear com ...
Страница 536: ...Courtesy of NationalSwitchgear com ...
Страница 550: ...Courtesy of NationalSwitchgear com ...
Страница 562: ...Courtesy of NationalSwitchgear com ...
Страница 570: ...Courtesy of NationalSwitchgear com ...
Страница 584: ...Courtesy of NationalSwitchgear com ...
Страница 602: ...Courtesy of NationalSwitchgear com ...
Страница 610: ...Courtesy of NationalSwitchgear com ...