SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Serial Port Communications and Commands
Command Explanations
Command Explanations
Access Level 0
Commands
ACC, BAC, and 2AC Commands (go to Access Level 1, B, or 2)
The
ACC
,
BAC
, and
2AC
commands provide entry to the multiple access
levels. Different commands are available at the different access levels as
shown in
. Commands
ACC
,
BAC
, and
2AC
are explained together
because they operate similarly.
➤
ACC
moves from Access Level 0 to Access Level 1.
➤
BAC
moves from Access Level 1 to Access Level B.
➤
2AC
moves from Access Level 1 or B to Access Level 2.
Password Requirements
Passwords are required if the main board Password jumper is not in place
(Password jumper = OFF). Passwords are not required if the main board
Password jumper is in place (Password jumper = ON). Refer to
for Password jumper information. See
for the list of default passwords and for more
information on changing passwords.
Access Level Attempt (Password Required)
Assume the following conditions: Password jumper = OFF (not in place),
Access Level = 0.
At the Access Level 0 prompt, enter the
ACC
command:
=
ACC <Enter>
Because the Password jumper is not in place, the relay asks for the Access
Level 1 password to be entered:
Password: ? @@@@@@
The relay is shipped with the default Access Level 1 password shown in the
table under
PAS Command (Change Passwords)
. At the prompt above, enter
the default password and press the
<Enter>
key. The relay responds:
FEEDER 1 Date: 03/05/01 Time: 08:31:10.361
STATION A
Level 1
=>
The
=>
prompt indicates the relay is now in Access Level 1.
If the entered password is incorrect, the relay asks for the password again
(
Password: ?
). The relay will ask up to three times. If the requested password
is incorrectly entered three times, the relay closes the
ALARM
contact for one
second and displays an invalid access message.
Содержание SEL-351-5
Страница 10: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 40: ...This page intentionally left blank ...
Страница 80: ...This page intentionally left blank ...
Страница 202: ...This page intentionally left blank ...
Страница 238: ...This page intentionally left blank ...
Страница 320: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 436: ...This page intentionally left blank ...
Страница 478: ...This page intentionally left blank ...
Страница 500: ...This page intentionally left blank ...
Страница 594: ...This page intentionally left blank ...
Страница 598: ...This page intentionally left blank ...
Страница 622: ...This page intentionally left blank ...
Страница 644: ...This page intentionally left blank ...
Страница 674: ...This page intentionally left blank ...
Страница 676: ...This page intentionally left blank ...