4-4
Event Reporting
Date Code 20011026
SEL-321/321-1 Instruction Manual
L
ONG
E
VENT
R
EPORT
The long event report is output in response to the EVENT x L command. The Header, Summary
and Settings sections of the long report are identical to the default report. The event report body
differs as follows:
The "L" format option increases the event report resolution to 16 samples/cycle. The bodies of
the 4 and 16 samples/cycle reports differ as follows:
•
The 16 samples/cycle report has four times as many data rows (total of 11 cycles
⋅
16
rows/cycle = 176 rows).
•
The element and contact input and output columns are sampled every 1/8-cycle, and
displayed in 1/16-cycle format. If an element asserts for 1/8-cycle, it would indicate
assertion for two rows in the long event report.
C
OMPUTER
E
VENT
R
EPORT
Generate the computer event report using the EVENT x C command. This format provides
complete relay element data by attaching a hexadecimal representation of the relay elements on a
per processing interval basis. This report is an 11-cycle duration, 16 samples/cycle report. All
inputs, outputs, and relay elements are shown in the computer event report.
U
NFILTERED
E
VENT
R
EPORT
Generate the unfiltered event report using the EVENT x U command. These reports are identical
to the EVE C event report, except that the analog data are not digitally filtered. Use the
unfiltered event report in computer analysis of data.
M
IRRORED
B
ITS
™ D
ISPLAY
E
VENT
R
EPORT
Generate an event report where TMB1...TMB8 replaces OUT1...OUT8 and RMB1...RMB8
replaces IN1...IN8 by appending any of the event report commands listed above with a space M.
With the exception of the display of the first eight inputs and outputs, the remainder of the M
form of the event report is identical.
I
NTERPRETATION OF
Q
UARTER
-C
YCLE
V
OLTAGE AND
C
URRENT
D
ATA
The relay uses secondary quantities presented to the input terminals of the relay. One line of
data is displayed for each quarter-cycle. Voltages and currents are shown in primary quantities.
The value in each column of the default event report is calculated and scaled as follows:
I
R
Calculated
I
R
value, multiplied by CTR from group active at time of trigger.
I
A
, I
B
, I
C
Sampled, filtered value, multiplied by CTR from group active at time of trigger.
V
A
, V
B
, V
C
Sampled, filtered value, multiplied by PTR from group active at time of trigger.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......