5-24
Trip and Target Logic
Date Code 20010625
SEL-311L Instruction Manual
D
IRECTIONAL
C
OMPARISON
U
NBLOCKING
(DCUB) L
OGIC
Enable the DCUB logic by setting ECOMM = DCUB1 or ECOMM = DCUB2. The DCUB logic
in Figure 5.12 is an extension of the POTT logic in Figure 5.8. Thus, the relay requires all the
POTT settings and logic, plus settings and logic exclusive to DCUB. The difference between
setting choices DCUB1 and DCUB2 is:
DCUB1
directional comparison unblocking scheme for two-terminal line
(communications from one remote terminal)
DCUB2
directional comparison unblocking scheme for three-terminal line
(communications from two remote terminals)
The DCUB logic in Figure 5.12 takes in the loss-of-guard and permissive trip outputs from the
communications receivers (see Figure 5.14 and Figure 5.15) and makes permissive
(PTRX1/PTRX2) and unblocking block (UBB1/UBB2) logic output decisions.
Use Existing SEL-321 Relay DCUB Application Guide for the SEL-311L Relay
Use the existing SEL-321 Relay DCUB application guide (AG96-19) to help set up the
SEL-311L Relay in a DCUB scheme (see preceding subsection
Communications-Assisted Trip
Logic
—
General Overview
for more setting comparison information on the SEL-321/SEL-311L
Relays).
External Inputs
See
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for
more information on optoisolated inputs.
PT1, PT2
x
Received Permissive Trip Signal(s)
In two-terminal line DCUB applications (setting ECOMM = DCUB1), a permissive trip signal is
received from one remote terminal. One optoisolated input on the SEL-311L Relay (e.g., input
IN104) is driven by a communications equipment receiver output (see Figure 5.14). Make
SEL
OGIC
control equation setting PT1:
PT1 = IN104
(two-terminal line application)
In three-terminal line DCUB applications (setting ECOMM = DCUB2), permissive trip signals
are received from two remote terminals. Two optoisolated inputs on the SEL-311L Relay (e.g.,
inputs IN104 and IN106) are driven by communications equipment receiver outputs (see
Figure 5.15). Make SEL
OGIC
control equation settings PT1 and PT2 as follows:
PT1 = IN104
(three-terminal line application)
PT2 = IN106
SEL
OGIC
control equation settings PT1 and PT2 are routed into the DCUB logic in Figure 5.12
for “unblocking block” and “permissive trip receive” logic decisions.
Содержание SEL-311L
Страница 6: ......
Страница 8: ......
Страница 26: ......
Страница 54: ......
Страница 144: ......
Страница 203: ...Date Code 20010625 Trip and Target Logic 5 27 SEL 311L Instruction Manual Figure 5 12 DCUB Logic ...
Страница 216: ......
Страница 252: ......
Страница 302: ......
Страница 338: ......
Страница 480: ......
Страница 484: ......
Страница 486: ......
Страница 502: ......
Страница 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Страница 552: ......
Страница 554: ......
Страница 574: ......
Страница 576: ......
Страница 596: ......
Страница 602: ......
Страница 628: ......
Страница 656: ......
Страница 662: ......
Страница 664: ......
Страница 688: ......
Страница 700: ......
Страница 716: ......
Страница 722: ......
Страница 734: ......