Date Code 20010625
Trip and Target Logic
5-5
SEL-311L Instruction Manual
B
ACKUP
P
ROTECTION
T
RIPS
The trip logic in Figure 5.4 provides flexible tripping with SEL
OGIC
control equation settings:
TRCOMM
Communications-Assisted Trip Conditions.
Setting TRCOMM is supervised by communications-assisted trip logic.
See
Communications-Assisted Trip Logic
—
General Overview
later in
this section for more information on communications-assisted tripping.
DTT
Direct Transfer Trip Conditions.
Note in Figure 5.4 that setting DTT is unsupervised. Any element that
asserts in setting DTT will cause Relay Word bit TRIP to assert to
logical 1.
Although setting TR is also unsupervised, setting DTT is provided
separately from setting TR for target LED purposes. (COMM target LED
on the front panel illuminates when DTT asserts to logical 1; see COMM
target LED discussion in the
Front-Panel Target LEDs
subsection at the
end of this section).
Typical settings for DTT are:
DTT = IN106 or DTT = RMB1A
where input IN106 is connected to the output of direct transfer trip
communications equipment or receive M
IRRORED
B
IT
RMB1A is asserted
by the transfer trip condition in a remote SEL relay.
Setting DTT is also used for Direct Underreaching Transfer Trip (DUTT)
schemes.
TRSOTF
Switch-Onto-Fault Trip Conditions.
Setting TRSOTF is supervised by the switch-onto-fault condition SOTFE.
See
Switch-Onto-Fault (SOTF) Trip Logic
information on switch-onto-fault logic.
TR
Other Trip Conditions.
Setting TR is the SEL
OGIC
control equation trip setting
most often used
if
tripping does not involve communications-assisted trip logic (settings
TRCOMM and DTT), switch-onto-fault (setting TRSOTF) trip logic, or
87L trip logic (use high-speed tripping via setting EHST).
OGIC
control equation trip setting TR is
unsupervised. Any element that asserts in SEL
OGIC
control equation
setting TR will cause Relay Word bit TRIP to assert to logical 1.
ULTR
Unlatch Trip Conditions.
TDURD
Minimum Trip Duration Time.
This timer establishes the minimum time duration for which the TRIP
Relay Word bit asserts. The settable range for this timer is 4–16,000
cycles.
Содержание SEL-311L
Страница 6: ......
Страница 8: ......
Страница 26: ......
Страница 54: ......
Страница 144: ......
Страница 203: ...Date Code 20010625 Trip and Target Logic 5 27 SEL 311L Instruction Manual Figure 5 12 DCUB Logic ...
Страница 216: ......
Страница 252: ......
Страница 302: ......
Страница 338: ......
Страница 480: ......
Страница 484: ......
Страница 486: ......
Страница 502: ......
Страница 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Страница 552: ......
Страница 554: ......
Страница 574: ......
Страница 576: ......
Страница 596: ......
Страница 602: ......
Страница 628: ......
Страница 656: ......
Страница 662: ......
Страница 664: ......
Страница 688: ......
Страница 700: ......
Страница 716: ......
Страница 722: ......
Страница 734: ......